NOTES ON DISPOSAL 

As a component of a large-scale fixed installation, Thermokon products are intended to be used permanently as part of a building 

or a structure at a pre-defined and dedicated location, hence the Waste Electrical and Electronic Act (WEEE) is not applicable. 

However, most of the products may contain valuable materials that should be recycled and not disposed of as domestic waste. 

Please note the relevant regulations for local disposal. 

» 

INFORMATION ABOUT INDOOR AIR QUALITY CO

2

 

EN 13779 defines several classes for indoor air quality: 

Category 

CO

2

 content above the content in outdoor air in ppm 

Description 

 

Typical range 

Standard value 

 

IDA1 

<400 ppm 

350 ppm 

Good indoor air quality 

IDA2 

400..   600 ppm 

500 ppm 

Standard indoor air quality 

IDA3 

600..1.000 ppm 

800 ppm 

Moderate indoor air quality 

IDA4 

>1.000 ppm 

1.200 ppm 

Poor indoor air quality 

» 

INFORMATION ABOUT SELF-CALIBRATION FEATURE CO

2

 

All gas sensors are subject to drift caused by components. This fact results generally in the need to recalibrate the sensors regularly. 
With dual channel technology Thermokon integrates automatic self-calibration for different fields of operation. In contrast to common used ABC-

Logic sensors with self-calibration dual channel are suitable for applications operating 24 hours, 7 days a week as for example hospitals. 

Manual calibration is not necessary! 

» 

TECHNICAL DATA 

Measuring values 

CO2 

Output voltage 

(type-dependent)

 

LA+ CO2 V

  

0..10 V, min. load10 kΩ

 

LA+ CO2 A

 

2x 0..10 V or 0..5 V, min load 10 kΩ

 

(live-zero configuration via Thermokon USEapp) 

Output ampere 

LA+ CO2 A

  

4..20 mA, max. load 500 Ω

 

Power supply 

(type-dependent)

 

LA+ CO2 V

 

15..35 V = or 19..29 V ~ SELV 

LA+ CO2 A

 

15..35 V = SELV

 

Power consumption 

max. 2,5 W (24 V =) | 4,3 VA (24 V ~) 

Measuring range CO2 

(type-dependent)

 

LA+ CO2 V

 

0..2000 ppm 

LA+ CO2 A

 

0..2000 ppm (Standard), 0..5000 ppm (optionally 

configured via Thermokon USEapp) 

Accuracy CO2 

±50 ppm +3% of reading (typ. at 70 °F, 50% rH) 

Calibration 

self-calibration, Dual Channel 

Sensor 

NDIR (non-dispersiv, infrared) 

Enclosure 

enclosure USE-M, PC, pure white, with removable cable entry 

Protection 

IP65 according to EN 60529 

Cable entry 

Flextherm M20, for wire max. Ø=0.18..0.35 in., removable 

Connection electrical 

removeable plug-in terminal, max. 14 AWG 

Ambient condition 

+32..+122 °F, max. 85% rH short term condensation 

Mounting 

installation is also possible using mounting base 

 

 

 