Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 141/162
Operating manual - translation into English © thermofin GmbH
Picture 104
Picture 105
Picture 103
Control valve 1 / 2
The current switch-on and switch-off limits of the adiabatic function are displayed in the
control valve
menu [No]
. However, the adiabatic is only activated if the ambient temperature limit is exceeded at
the same time (see 7.4.4. “
”). The menu is closely linked to the
efficiencySLIDE
menu, with the
efficiencySLIDE
is at the higher level.
The switch-on and switch-off limits are determined by the speed and the possible air pre-cooling.
They are dependent on each other in a ratio that can be set in the “efficiencySLIDE” submenu. As a
result, all main settings must be made there (see 7.4.6 “
”). The position of the
efficiencySLIDE
is displayed in the mat menu (see Picture 99).
If the user changes one of the four switching limits for adiabatic mode in the
Control valve
menu, all other values change automatically. The
efficiencySLIDE
is thus shifted indirectly.
A change in the switch-on speed of the adiabatic shifts, for example, all other switching limits
(see Picture 103 and Picture 104).
Display of mat menu:
75 %
→90 %
Display:
Possible pre-cooling, speed output
circuit 1 and valve position
①
②
③
④
⑤
⑥
Display: Summer /
Winter operation