8.1
Mertik GV60 Troubleshooting Flow Chart
No ACTION
Possible problem/cause
Solution
1.
Option: wall switch START:
press ON button > wall switch
works.
NO
Bent pin on switch, or cable not
operating properly.
Straighten pin, replace wall switch
or cable.
1.
Manual transmitter START: press
both buttons to start ignition
sequence.
Beep will occur each second
NO
Manual transmitter battery low.
Replace battery, 9V quality
alkaline!
Receiver batteries low.
Replace batteries, 1.5V AA quality
alkaline!
Optional mains adapter not
operating properly.
Check mains adapter.
Check coding of transmitter and
receiver.
Learn in new code, see instructions
and label on receiver.
OK
Transmitter/receiver range
limited.
1.
Move antenna cable, see
instructions.
2.
Replace receiver.
Optional wall switch / cabling not
operating properly.
Replace wall switch / cabling.
Receiver fuse blown (in older
versions only).
Replace receiver.
2.
Magnet unit in gas valve is
energised (audible click)
NO
No beep
Impulse magnet not operating
properly.
Replace gas valve.
NO
3 short beeps Receiver batteries low.
Replace batteries, 1.5V AA quality
alkaline!
NO
1 long beep
ON/OFF switch on gas valve in
OFF position
Set switch to ON.
8-wire cable between receiver and
gas valve defective / poor contact.
Check cable, especially in case of
plug connection.
OK
Switch cable disconnected.
Check switch cable, see fig. 1 on
page 18
Motor not operating properly.
Replace gas valve.
Micro switch on gas valve not
operating properly.
Replace gas valve.
Содержание Trimline 2050 OH
Страница 1: ...Page 1 OPERATING AND INSTALLATION INSTRUCTIONS 1080 Trimline 2050 OH UNITED KINGDOM UK IRELAND IE...
Страница 20: ...Page 20...
Страница 32: ...Pag 32 A...
Страница 33: ...Pag 33 20 m m B C D E F G...
Страница 34: ...Pag 34 I J 50 20 H...
Страница 35: ...Pag 35...
Страница 36: ...Pag 36...
Страница 37: ...Pag 37...
Страница 38: ...Pag 38...
Страница 39: ...Pag 39...
Страница 40: ...Pag 40 Thermocet International B V Laagerfseweg 31 3931 PC Woudenberg www thermocet nl...