Common DD Calibration Method
With all 3 inputs, the calibration method/procedure is identical.
In this section we look at the calibration procedure for the RTD temperature input.
Both DP and Pressure inputs will follow the same sequence.
1. After selection of the required input for calibration
,
a warning is provided to
remove the AutoXP MVT output from any automatic control.
Figure 4-92. Calibrate RTD Input
2. Select the required number of calibration points.
Here we are selecting a Three Point Calibration.
Figure 4-93. Three Point Calibration
4-52 AutoXP Users Guide
Thermo Fisher Scientific