All installations and services must be performed by qualified service personnel. 

11 

Dehumidification Operation 

If a call for dehumidification is received while the Cool Mode is active, blower speeds will be reduced.  
The speed value will be selected from the DEHUM column of the CFM Tables.  This input may only be 
used on systems using a thermostatic expansion valve (TXV) on the evaporator. 

Anti-Short Cycle Operation 

To prevent compressor short cycling, a call for cooling will be ignored for four minutes after the 
termination of any cooling call.  The anti-short cycle delay is also in effect at power-up.  

Heat Mode 

When a call for heat ("W") is received from the thermostat, if the “Cool” mode is not already active, the “T-T” 
terminal is energized and the blower on delay is started.  The on-off pattern of DIP switch SW2 (positions 1 
and 2) select one of four blowers on delay values (see Table 1).  When the delay time has elapsed, a speed 
value is read from DIP switch SW1 positions 1 through 3 (see the CFM Tables) and the blower is ramped up 
to that speed.  The 2-Stage control will be operated by t-stat through W1 and W2.  For 2-stage control with a 
single stage t-stat, call for heat will go through W2.  When W2 is energized, low fire is activated for 15 
minutes.  If a call for heat still exists, high fire will be activated and will continue until the demand for heat 
has been satisfied. 

Counterflow units, in addition, will run at a low blower speed shortly after the burner is brought on.  They will 
continue at that speed until the delay time has elapsed. 

The control remains in steady heat mode until the thermostat is satisfied.  When the call for heat signal is 
removed, the “T-T” terminal is de-energized and the blower off delay is started.  The on-off pattern of DIP 
switch SW2 (positions 3 and 4) select one of four blower off delay values (see Table 1).  When the delay time 
has elapsed, the blower is ramped toward zero.

 

Table 1:

 ON and OFF Blower Delay Time Switch Settings  

DIP SWITCH 2 SECTION 
STATE 

BLOWER DELAY 

TIMES 

 

1

 

ON - SEC

 

OFF - MIN

 

 

OFF 

OFF 

 

 

30 

 

 

OFF 

ON 

 

 

60 

 

 

ON 

OFF 

 

 

120 

 

Factory Set 

ON 

ON 

 

 

240 

 

 

 

 

OFF 

OFF 

 

 

 

 

OFF 

ON 

 

 

 

 

ON 

OFF 

 

Factory Set 

 

 

ON 

ON 

 

 

 
Motor Blower Speed  

Three blower speed outputs are provided.  A “G” call for fan will provide the Low speed only.  A “W” 
heat call will provide the Heat speed only.  A “Y” cooling call will provide the Cool speed only. 
 
In the case of thermostat calls for “Y” and “W” together, blower speed selection will be determined by the 
input that was first initiated.   In the case where the control is in a cooling mode with both “Y” and “W” 
inputs energized and then the “Y” input is removed, the cooling blower off time will be executed prior to 
the control switching into a heating mode.  In the case where the control is in a heating mode with both 
“Y” and “W” inputs energized and then the “W” input is removed, the heating blower off time will be 
executed prior to the control switching into a cooling mode.  In the case where a call for fan “G” already 
exists and either a “W” or a “Y” call is initiated, the blower speed will switch to the respective “W” or a 
“Y” speed following the blower on delay for that call. 

Содержание OC2-56DE

Страница 1: ...GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER REF...

Страница 2: ...SHIPPED SETTINGS 1 II BLOWER CONTROL INFORMATION 4 A TERMINAL DEFINITIONS FIELD WIRING 4 B WIRING SWITCHES 5 C INPUTS 9 D OUTPUTS 9 E OPERATING MODES 10 F CFM TABLES 12 G ECM SPECIFIC REPLACEMENT PAR...

Страница 3: ...TION CFM 1000 1000 1000 3 SWITCH SELECTION CFM 1200 1200 1200 3 1 2 TON SWITCH SELECTION CFM 1400 1400 1400 HEATING HEATING HEATING 70deg SWITCH SELECTION CFM 737 1134 1335 APPROX TEMPERATURE RISE F 7...

Страница 4: ...TION CFM 1000 1000 1000 924 3 SWITCH SELECTION CFM 1200 1200 1200 1276 3 1 2 TON SWITCH SELECTION CFM 1400 1400 1400 1474 4 TON 1600 HEATING HEATING HEATING HEATING 70deg SWITCH SELECTION CFM 737 1134...

Страница 5: ...ION CFM 1200 1200 3 1 2 TON SWITCH SELECTION CFM 1400 1400 HEATING HEATING 70deg SWITCH SELECTION CFM 737 1134 APPROX TEMPERATURE RISE F 70 70 BLOWER MOTOR HP 1 2 1 2 NOZZLE SIZE 55 75 NOZZLE SPRAY AN...

Страница 6: ...ostat call for heat R 24 VAC to thermostat G Thermostat call for fan Y Thermostat call for cool DEHUM Humidistat call for dehumidification TXV systems ONLY Thermostat Humidistat connections for 2 Stag...

Страница 7: ...All installations and services must be performed by qualified service personnel 5 B WIRING SWITCHES HIGHBOY LOWBOY Figure 1 BLOWER WIRING...

Страница 8: ...installations and services must be performed by qualified service personnel 6 TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring COUNTERFLOW Figure 2 BLOWER WIR...

Страница 9: ...tallations and services must be performed by qualified service personnel 7 TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring OH5 85 DXE 2 STAGE Figure 3 BLOWER...

Страница 10: ...lations and services must be performed by qualified service personnel 8 TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring Figure 2 BOARD LAYOUT WITH SWITCHES B...

Страница 11: ...oling is recognized when the thermostat connects Y to R This input has an indicator LED that will light when the control receives a call for cooling Refer to the Cool Mode section for the control oper...

Страница 12: ...flash once for every 100CFM the blower is producing E Operating Modes Standby Mode All outputs are off and the control is waiting for a thermostat demand The thermostat inputs and limit switch are co...

Страница 13: ...the burner is brought on They will continue at that speed until the delay time has elapsed The control remains in steady heat mode until the thermostat is satisfied When the call for heat signal is re...

Страница 14: ...s F CFM TABLES The following tables contain blower speed settings and their respective air flowrates for the ECM blower motor To change air flowrates from that of the shipped settings use the respecti...

Страница 15: ...r 350464 350464 350464 350464 350464 350464 III ECM TROUBLE SHOOTING A DIAGNOSTC FEATURES The control board is equipped with 4 green Input Status LEDs and 1 red Board Status LED These are intended to...

Страница 16: ...motor for tight shaft Perform motor control replacement check Run Moisture Check Motor rocks but won t start Check for loose or compliant motor mount Make sure blower wheel is tight on shaft Perform...

Страница 17: ...motor is bad Orient connectors down so water can t get in Install drip loops Locate connectors above 7 and 4 o clock positions Use authorized motor and control model s for replacement Replace one moto...

Страница 18: ...ce personnel 16 Low static pressure for lowest noise Set low continuous fan CFM T stat in bad location Figure 3 ECM PIN CONNECTORS Troubleshooting table above and Figure 2 adapted from GE Industrial S...

Страница 19: ...TO MOTOR IF CONNECTIONS ARE GOOD AND MOTOR STILL DOES NOT RUN REPLACE MOTOR THIS GUIDE SHOULD BE USED IN THE CASE OF A STOPPED OR MANFUNCTIONED ECM BLOWER MOTOR THE FOLLOWING SHOULD HELP ESTABLISH THE...

Страница 20: ...Status LED Off 1 HEAT mode On 2 BLOWER HEAT 3 Status LED Flashes 1 COOL mode On 2 Blower On Delay Started 3 Condenser On 4 Status LED On continuous 1 FAN mode On 2 BLOWER LOW 3 Status LED On continuo...

Страница 21: ...Fire Connect 2 Stage T stat to both W1 and W2 Single Stage T stat W2 Connect single stage T stat to W2 only BLOWER Speeds HEAT The Heating Blower speed selected by positions 1 2 3 of SW1 CFM tables o...