background image

All installations and services must be performed by qualified service personnel. 

10 

The switched 120VAC power from the LIMIT switch passes through the board between Pins 1&2 
of connector P1. 

 

Compressor contactor 

The control provides switched 24VAC to operate a compressor contactor.  Rating shall be class 2 - 24 
VAC pilot duty @ 24 VAC (< 200mA).   

EAC (electronic air cleaner) 

The control provides a 120VAC output for an electronic air cleaner. This output is energized whenever the fan 
motor is energized (either low, heat or cool speed).  Connection is made via male quick connect terminal 
labeled "EAC".

 

 

Humidifier

 

 

The control provides a 120 VAC output for a humidifier.  Connections are made to a male quick connect 
terminal labeled "HUM".  The control does not switch this output, it provides a pass-through connection from 
P1-7 from the switched primary voltage of the Burner Module. 

 

Status LED 

A red LED is provided to indicate any thermostat input has been recognized by the microprocessor on the 
control.  See Diagnostic Features for a function description of operation.   

Thermostat Input LEDs 

Four green LEDs are placed beneath their respective thermostat connections (W, Y, G and DEHUM) and 
operate whenever a call is present.  See Diagnostic Features for a function description of operation.   

Motor CFM LED 

 

This green LED will flash once for every 100CFM the blower is producing.

 

E.  Operating Modes 

 
Standby Mode 

All outputs are off and the control is waiting for a thermostat demand.  The thermostat inputs, and limit 
switch are continuously monitored.  The control initiates action when a thermostat call is received or limit 
switch opens. 

 Fan Mode  

A call for fan ("G") is received from the thermostat.  If no other mode is calling for blower operation, the 
control will choose a “Low” speed value from the position of DIP switch SW1 positions 4 through 6, as 
shown in the CFM Tables and operate the fan at that speed.  The fan mode will be operated as long as the 
"G" input is calling

 

and neither the Heat mode nor the Cool mode is calling for blower operation. When the 

Heat and Cool modes call for blower operation, their respective outputs will take over after their respective 
turn-on time delays have expired. The speed Output is present until the fan call is satisfied. 

Cooling Mode 

A call for cool ("Y") is received from the thermostat.  If the heat mode is not active or the anti-short cycle 
delay is not in effect, the control will energize the “CC” terminal.  After a 10 second delay blower ramps up to 
the “COOL” speed determined by the position of DIP switch SW1 (positions 4 through 6) determine a speed as 
shown in CFM Tables. 

When the call for cool is satisfied, the “CC” terminal is de-energized and the cooling off delay of 45 seconds is 
started.  Forty-five seconds later the blower speed ramps toward zero and the control reverts to Standby Mode. 

Содержание OC2-56DE

Страница 1: ...GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER REF...

Страница 2: ...SHIPPED SETTINGS 1 II BLOWER CONTROL INFORMATION 4 A TERMINAL DEFINITIONS FIELD WIRING 4 B WIRING SWITCHES 5 C INPUTS 9 D OUTPUTS 9 E OPERATING MODES 10 F CFM TABLES 12 G ECM SPECIFIC REPLACEMENT PAR...

Страница 3: ...TION CFM 1000 1000 1000 3 SWITCH SELECTION CFM 1200 1200 1200 3 1 2 TON SWITCH SELECTION CFM 1400 1400 1400 HEATING HEATING HEATING 70deg SWITCH SELECTION CFM 737 1134 1335 APPROX TEMPERATURE RISE F 7...

Страница 4: ...TION CFM 1000 1000 1000 924 3 SWITCH SELECTION CFM 1200 1200 1200 1276 3 1 2 TON SWITCH SELECTION CFM 1400 1400 1400 1474 4 TON 1600 HEATING HEATING HEATING HEATING 70deg SWITCH SELECTION CFM 737 1134...

Страница 5: ...ION CFM 1200 1200 3 1 2 TON SWITCH SELECTION CFM 1400 1400 HEATING HEATING 70deg SWITCH SELECTION CFM 737 1134 APPROX TEMPERATURE RISE F 70 70 BLOWER MOTOR HP 1 2 1 2 NOZZLE SIZE 55 75 NOZZLE SPRAY AN...

Страница 6: ...ostat call for heat R 24 VAC to thermostat G Thermostat call for fan Y Thermostat call for cool DEHUM Humidistat call for dehumidification TXV systems ONLY Thermostat Humidistat connections for 2 Stag...

Страница 7: ...All installations and services must be performed by qualified service personnel 5 B WIRING SWITCHES HIGHBOY LOWBOY Figure 1 BLOWER WIRING...

Страница 8: ...installations and services must be performed by qualified service personnel 6 TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring COUNTERFLOW Figure 2 BLOWER WIR...

Страница 9: ...tallations and services must be performed by qualified service personnel 7 TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring OH5 85 DXE 2 STAGE Figure 3 BLOWER...

Страница 10: ...lations and services must be performed by qualified service personnel 8 TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring Figure 2 BOARD LAYOUT WITH SWITCHES B...

Страница 11: ...oling is recognized when the thermostat connects Y to R This input has an indicator LED that will light when the control receives a call for cooling Refer to the Cool Mode section for the control oper...

Страница 12: ...flash once for every 100CFM the blower is producing E Operating Modes Standby Mode All outputs are off and the control is waiting for a thermostat demand The thermostat inputs and limit switch are co...

Страница 13: ...the burner is brought on They will continue at that speed until the delay time has elapsed The control remains in steady heat mode until the thermostat is satisfied When the call for heat signal is re...

Страница 14: ...s F CFM TABLES The following tables contain blower speed settings and their respective air flowrates for the ECM blower motor To change air flowrates from that of the shipped settings use the respecti...

Страница 15: ...r 350464 350464 350464 350464 350464 350464 III ECM TROUBLE SHOOTING A DIAGNOSTC FEATURES The control board is equipped with 4 green Input Status LEDs and 1 red Board Status LED These are intended to...

Страница 16: ...motor for tight shaft Perform motor control replacement check Run Moisture Check Motor rocks but won t start Check for loose or compliant motor mount Make sure blower wheel is tight on shaft Perform...

Страница 17: ...motor is bad Orient connectors down so water can t get in Install drip loops Locate connectors above 7 and 4 o clock positions Use authorized motor and control model s for replacement Replace one moto...

Страница 18: ...ce personnel 16 Low static pressure for lowest noise Set low continuous fan CFM T stat in bad location Figure 3 ECM PIN CONNECTORS Troubleshooting table above and Figure 2 adapted from GE Industrial S...

Страница 19: ...TO MOTOR IF CONNECTIONS ARE GOOD AND MOTOR STILL DOES NOT RUN REPLACE MOTOR THIS GUIDE SHOULD BE USED IN THE CASE OF A STOPPED OR MANFUNCTIONED ECM BLOWER MOTOR THE FOLLOWING SHOULD HELP ESTABLISH THE...

Страница 20: ...Status LED Off 1 HEAT mode On 2 BLOWER HEAT 3 Status LED Flashes 1 COOL mode On 2 Blower On Delay Started 3 Condenser On 4 Status LED On continuous 1 FAN mode On 2 BLOWER LOW 3 Status LED On continuo...

Страница 21: ...Fire Connect 2 Stage T stat to both W1 and W2 Single Stage T stat W2 Connect single stage T stat to W2 only BLOWER Speeds HEAT The Heating Blower speed selected by positions 1 2 3 of SW1 CFM tables o...

Отзывы: