Nozzle
Check pump pressure with pump
Nozzle overfiring due to high
Reduce pump pressure according
gauge.
pump pressure.
to installer/serviceman labels
starting on page 30.
Heat
Check heat exchanger surfaces
Heat exchanger fouled.
Clean heat exchanger.
Exchanger
for soot or scale fouling.
Baffles
Check baffles installed.
Baffles not installed.
Install baffles.
SOURCE
PROCEDURE
CAUSES
REMEDY
TROUBLE: HIGH NET STACK TEMPERATURES
Tankless
Analyze capacity vs. usage.
Insufficient coil capacity.
Install larger coil.
Coil
Operating
Check operating control.
Setting too low.
Set operating control to 180°F.
Control
Raise differential set point.
Heat
Inspect coils for fouled surfaces
Flow restriction.
Remove restriction.
Exchanger
and/or flow restrictions.
Fouled surfaces on heat exchanger.
Clean heat exchanger surfaces.
SOURCE
PROCEDURE
CAUSES
REMEDY
TROUBLE: INSUFFICIENT DOMESTIC HOT WATER
SERVICE SET-UP TIPS
COMBUSTION EFFICIENCY = CO2 vs. Stack Temp.
When using the rear vent flue box with integral draft regulator, combustion testing can be taken through the fire port above
the burner. Insert your probe approximately 1/2" to 1" or through a 1/4" hole in the top of the flue box. Locate hole in front
right fire tube (see illustration on page 4). Stack temperature can be taken through a drilled hole in the flue box. To minimize
air dilution, hold draft regulator in a closed position. (See page 4)
BURNER AIR refer to page 5 concerning air for combustion, ventilation, and placement of the boiler in a utility room or
closet. This also addresses special conditions where a boiler is located in an area of operation next to ex haust fans, kitchen
ventilation systems, clothes dryers, etc...(See Section V).
Draft overfire all models 0 to +.10
Draft in stack all models - .02 Min.
CO2 readings all models 10 - 11.5%
Smoke reading all models 0
- NOTICE -
Above settings are approximate. Final adjustments to be made with proper test equipment. Be sure oil lines are air free
and the use of flare fittings is recommended. See installation/service manual for detailed information.
Alternate Nozzles for AFG
1 .75 - 70°B HAGO
2 .85 - 80°A DELAVAN OR .85 80°B HAGO
3 1.00 - 80°A DELAVAN OR 1.00-80°A HAGO
23