INSTALLER/SERVICEMAN
Model Number STR-85
Burner Type Beckett Carlin Riello
Burner Model AFG* EZ-1 F5
Nozzle Type 0.65 80B 0.65 60A 0.65 60A
Pump Pressure PSI 140 140 150
Head/Pin Position F-3 85-100 1.5
Air Band CLOSED 0.85 N/A
Air Shutter 10 N/A 1.75
Draft Over Fire -0.02" -0.02" -0.02"
Draft In Stack -0.05" -0.05" -0.05"
CO2 Reading 10-11.5 10-11.5 10-11.5
Smoke Reading ZERO ZERO ZERO
*With AFG use low firing rate baffle
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. Be sure all oil lines are air free and
the use of flare fittings is recommended. See installation/service
manual for detailed information.
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
INSTALLER/SERVICEMAN
Model Number STR-100
Burner Type Beckett Carlin Riello
Burner Model AFG EZ-1 F5
Nozzle Type 0.75 80B 0.75 60A 0.75 60A
Pump Pressure PSI 140 140 150
Head/Pin Position F-3 85-100 2.0
Air Band CLOSED 1.00 N/A
Air Shutter 8 N/A 4
Draft Over Fire -0.02" -0.02" -0.02"
Draft In Stack -0.05" -0.05" -0.05"
CO2 Reading 10-11.5 10-11.5 10-11.5
Smoke Reading ZERO ZERO ZERO
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. Be sure all oil lines are air free and
the use of flare fittings is recommended. See installation/service
manual for detailed information.
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
INSTALLER/SERVICEMAN
Model Number STR-110
Burner Type Beckett Carlin Riello
Burner Model AFG EZ-1 F5
Nozzle Type .85 80B 0.85 60A 0.85 60A
Pump Pressure PSI 140 140 150
Head/Pin Position F-3 110-125 2.5
Air Band CLOSED 1.10 N/A
Air Shutter 10 N/A 4
Draft Over Fire -0.02" -0.02" -0.02"
Draft In Stack -0.05" -0.05" -0.05"
CO2 Reading 10-11.5 10-11.5 10-11.5
Smoke Reading ZERO ZERO ZERO
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. Be sure all oil lines are air free and
the use of flare fittings is recommended. See installation/service
manual for detailed information.
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
Appendix F
STR Energy Star Product