31
INSTALLER/SERVICEMAN
Model Number
HT-165
HT-175
HT-200
Burner Type
Beckett
Beckett
Beckett
Burner Model
AFG
AFG
AFG
Nozzle Type
1.50 60B
1.65 60B
1.75 60B
Pump Pressure PSI
140
140
140
Head/Pin Position
M-2
M-3
M-3
Air Band
5
5
7
Air Shutter
OPEN
OPEN
OPEN
Draft Over Fire
+.06"
+.08"
+0.10"
Draft In Stack
-0.02"
-0.02"
-0.02"
CO2 Reading
10-11.5
10-11.5
10-11.5
Smoke Reading
ZERO
ZERO
ZERO
NOTE: Pressure over fire will vary according to CO2 setting.
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. Be sure all oil lines are air free and
the use of flare fittings is recommended. See installation/ser-
vice manual for detailed information.
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
INSTALLER/SERVICEMAN
Model Number
HT-225
HT-250
HT-275
Burner Type
Beckett
Beckett
Beckett
Burner Model
CF-375
CF-375
CF-375
Nozzle Type
2.00 60B
2.25 60B
2.50 60B
Pump Pressure PSI
140
140
140
Head/Pin Position
3
3
4
Air Band
3
6
6
Air Shutter
OPEN
OPEN
OPEN
Draft Over Fire
+.06"
+.09"
+0.11"
Draft In Stack
-0.02"
-0.02"
-0.02"
CO2 Reading
10-11.5
10-11.5
10-11.5
Smoke Reading
ZERO
ZERO
ZERO
NOTE: Pressure over fire will vary according to CO2 setting.
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. Be sure all oil lines are air free and
the use of flare fittings is recommended. See installation/ser-
vice manual for detailed information.
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
INSTALLER/SERVICEMAN
Model Number
HT-125
HT-135
HT-150
Burner Type
Riello
Riello
Riello
Burner Model
F5
F5
F5
Nozzle Type
1.00 60B
1.10 60B
1.25 60B
Pump Pressure PSI
150
150
150
Head/Pin Position
2.5
3.5
4.0
Air Band
N/A
N/A
N/A
Air Shutter
3.0
3.5
4.5
Draft Over Fire
+.03"
+.05"
+.07"
Draft In Stack
-0.02"
-0.02"
-0.02"
CO2 Reading
10-11.5
10-11.5
10-11.5
Smoke Reading
ZERO
ZERO
ZERO
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. Be sure all oil lines are air free and
the use of flare fittings is recommended. See installation/ser-
vice manual for detailed information.
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
INSTALLER/SERVICEMAN
Model Number
HT DV-125
HT DV-125 HT DV-125
Burner Type
Beckett
Carlin*
Riello
Burner Model
AFII
EZ-1
BF5
Nozzle Type
1.00 60°B
1.00 60°B
1.00 60°B
Pump Pressure PSI
140
140
150
Head/Pin Position
7.0
0.85-1.00
2.0
Air Band
N/A
N/A
N/A
Air Shutter
6.0
6.0
6.0
Draft Over Fire
+.0.16
+.0.14
+0.13
Draft In Stack
-0.08
-0.07
-0.07
CO2 Reading
10-11.5%
10-11.5%
10-11.5%
Smoke Reading
ZERO
ZERO
ZERO
*Requires Carlin Air Intake Adapter
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. Be sure all oil lines are air free and
the use of flare fittings is recommended. See installation/ser-
vice manual for detailed information.
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________
________________________