ENGLISH
LENGTH, SIZE WIRES AND DELAYED FUSE
l
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with
foamed polyethylene (min. thickness 8mm).
l
PVC pipe for condensate drain pipe (ø int.18mm) in length suitable to let the condensate flow into the outside drainage.
l
Anti-freeze oil for flare connections (about 30g.).
l
Electric wire: use insulated copper wires of size and length as shown at paragraph “SYSTEM WIRING DIAGRAMS”.
Supply power wire A:
Multipolar electric wire. Size and length of the suggested electric wire are showed on table “electrical data”. The wire
must be Mod. H07RN-F (according to CEI 20-19 CENELEC HD 22). Make sure the length of the conductors between
the fixing point and the terminals allows the straining of the conductors L, N before that of the grounding.
Connecting wire B (SHIELDED):
Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table “electrical data”.
The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).
Connecting wire C (with ground conductor):
Multipolar electric wire; size and length of the suggested electric wire are showed on table “electrical data”. The
wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22).
NARROW TUBE
LARGE TUBE
INDOOR UNIT SIZE
OUTER DIAMETER
MIN. THICKNESS
OUTER DIAMETER
MIN. THICKNESS
A
6,35 mm
0,8 mm
9,52 mm
0,8 mm
B - C - D
6,35 mm
0,8 mm
12,7 mm
0,8 mm
l
Cooling Maximum conditions
Outdoor temperature : 43°C D.B.
Room temperature :
32°C D.B. / 23°C W.B.
l
Cooling Minimum conditions
Outdoor temperature : –15°C D.B.
Room temperature : 10°C D.B. / 6°C W.B.
l
Heating Maximum conditions
Outdoor temperature : 24°C D.B. / 18°C W.B.
Room temperature :
27°C D.B.
l
Heating Minimum conditions
Outdoor temperature : –15°C D.B.
Room temperature : 5°C D.B.
OPERATING LIMITS
7
LENGTH, SIZE WIRES AND DELAYED FUSE
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
l
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with
foamed polyethylene (min. thickness 8mm).
l
PVC pipe for condensate drain pipe (ø int.18mm) in length suitable to let the condensate flow into the outside drainage.
l
Anti-freeze oil for flare connections (about 30g.).
l
Electric wire: use insulated copper wires of size and length as shown at paragraph “SYSTEM WIRING DIAGRAMS”.
Supply power wire A:
Multipolar electric wire. Size and length of the suggested electric wire are showed on table “electrical data”. The wire
must be Mod. H07RN-F (according to CEI 20-19 CENELEC HD 22). Make sure the length of the conductors between
the fixing point and the terminals allows the straining of the conductors L, N before that of the grounding.
Connecting wire B (SHIELDED):
Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table “electrical data”.
The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).
Connecting wire C (with ground conductor):
Multipolar electric wire; size and length of the suggested electric wire are showed on table “electrical data”. The
wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22).
NARROW TUBE
LARGE TUBE
INDOOR UNIT SIZE
OUTER DIAMETER
MIN. THICKNESS
OUTER DIAMETER
MIN. THICKNESS
A
6,35 mm
0,8 mm
9,52 mm
0,8 mm
B - C - D
6,35 mm
0,8 mm
12,7 mm
0,8 mm
Cooling Maximum conditions
Outdoor temperature : 43°C D.B.
Room temperature :
32°C D.B. / 23°C W.B.
Cooling Minimum conditions
Outdoor temperature : –15°C D.B.
Room temperature :
10°C D.B. / 6°C W.B.
Heating Maximum conditions
Outdoor temperature : 24°C D.B. / 18°C W.B.
Room temperature :
27°C D.B.
Heating Minimum conditions
Outdoor temperature : –15°C D.B.
Room temperature :
5°C D.B.
OPERATING LIMITS
MODEL
AFEX 080
mm
2
20 A
1 UNIT
2 UNITS
3 UNITS
4 UNITS
AFEX 110
mm
2
25 A
1 UNIT
2 UNITS
3 UNITS
AFEX 110
3PH
4 UNITS
12,5 A
30
20
30
30
1,5
20
50
50
20
30
30
20
30
4
30
0,75
30
L ("A") m
L ("B") m
L ("C") m
2,5
0,75
1,5
30
20
30
20
30
30
20
50
50
20
EG
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
15
Содержание AFEX 080 MONO
Страница 4: ...ITALIANO 4 UNIT INTERNE 1 FASE 1 FASE 3 UNIT INTERNE 4...
Страница 5: ...ITALIANO 1 UNIT INTERNA 2 UNIT INTERNE 3 FASI 3 FASI 5...
Страница 12: ...ENGLISH 3 INDOOR UNITS 4 INDOOR UNITS 1 PHASE 1 PHASE 12...
Страница 13: ...ENGLISH 1 INDOOR UNIT 2 INDOOR UNITS 3 PHASE 3 PHASE 13...
Страница 31: ...31...