12
OwNER’s mANuAl
CHAuFFE-PIsCINE
COMMERCIAL
POOl HEAT PumP
3 Phase loss and reversal protection
Operating mode:
The THERmEAu unit is equipped with sCROll
compressor which cannot run in both rotations.
when the heating light on the main board will come
on, If all three phase are relatively equal and in pro-
per sequence, the (ON) green light on the phase
protector will be energize and the compressor will
start normally. If the phase are in wrong sequence,
that’ll be the (FAulT) red light that come ON and the
compressor won’t start. If this occurred, you have to
switch the l1 wire with l2 wire.
WARNING
l 3
l 2
l 2
l1
l1
Ground
Ground
ON
FAulT
Electrical Connections
The installation of the THERmEAu pool heater should be performed by a cer-
tified electrician. To connect the electricity, you must unscrew the four screws
of the front panel, then slide the electric cable in the hole located on the left
or the right side of the base, and then insert it in the control box. The electrical
diagram is located on the lid of the control box as well as below.