4. Installation
4.1 Location
The Quest 335 Dehumidifer can be installed in a variety of locations to meet the owner’s needs as listed below. In all
cases keep the following cautions in mind:
• Place the Quest 335 Dehumidifer on supports that raise the base of the unit 6” above the secondary drain pan so a
P-trap can be installed. See Section 4.3.
• The Quest 335 Dehumidifer may be suspended with steel hanger, straps, or a suitable alternative from structural
members, unit must be supported from underneath. Don’t hang from sides or ends. See section 4.4
• If installing on ground, use included plugs to cover hanging locations on top of the machine.
• If hanging machine in air, use included plugs to cover holes in base pan for leveling feet.
4.2 Electrical Requirements
The Quest 335 Dehumidifer plugs into NEMA rated receptacles. The amp draws for each unit under normal operating
conditions are listed on page 4. A ground fault interrupter protected circuit is required.
Install the remote hygrostat in a central area of the structure where it will sense the relative humidity of the structure
accurately. Do not install the hygrostat where it may not accurately sense the relative humidity such as near HVAC
supply registers, near exterior doors, or near a pool or spa. The installer must supply the wiring between the Quest 335
Dehumidifer and the hygrostat. Be sure to safely route the control wiring to prevent damage during installation. Be
careful not to cross the wires when connecting the Quest 335 Dehumidifer and the remote hygrostat.
The remote controls of the Quest 335 Dehumidifer are powered by a low voltage circuit (24 VAC) and must NEVER
contact or be connected to a high voltage circuit. The control terminals and remote control are labeled and numbered to
prevent confusion. Be sure to consult the electrical schematic in this manual or inside the access panel of the Quest 335
Dehumidifer before making the control connections.
CAUTION! Always disconnect the Quest 335 from a power source when working with the low
voltage control wires.