If the pump fails, this switch opens the compressor control circuit and stops water production before the reservoir
overfows. The Quest 335 Dehumidifer will continue to ventilate or circulate air as normal, but will not dehumidify until
this switch closes.
8. Quest 335 Error Codes
1 RH Sensor
Error
No valid RH reading for ~ 22
seconds
Disregard for terminal control
display “--”
Valid RH reading
Error Code: “E1”
Circulate: 1 minute
Dehumidistat: 15 minutes
Dehu mode: 15 minutes
Repeat
Detected on power board, error
communicated to UI
3
Out of
Refrigerant
Evaporator doesn’t get at least
5°F below ambient after being
in dehumidification mode for
10 minutes or more
Lock-out for 1 hour
Re-start and see if
evaporator gets cold
again
Error Code: “E3”
Compressor off (during lock-out)
Fan off (during lock-out)
Goes to circulate mode
4
Normally
Closed (NC)
Float Switch
Tripped
The FLOAT terminals on the
UI are in error state. If it is
open for ~ 6 seconds this alert
will trigger. This should happen
in all states (not just when in
Terminal control)
Float inputs are open
Error code: “E4”
Compressor off, fan off
Use command Set:
Dehu_state:off
5 Evaporator
Sensor Error
Invalid reading (above 200°F
or below -20°F) from the
evaporator sensor for ~ 12
seconds or more
Valid evaporator sensor
reading for ~ 12 seconds
or more
Error code: “E5”
Dehu Mode: 15 minutes
Defrost Mode: 30 Minutes
Repeat
6 Temperature
too High
Either the evaporator or the
ambient sensor is reading
above 120°F
Lock-Out for 1 hour
temperatures drop
below threshold
Error Code: “E6”
Fan off
Compressor off
7 Temperature
too Low
Ambient sensor reading
was under 40°F when the
dehumidifier was either in
dehu or circulate mode: The
unit will enter dehumidistat
mode and stay there for at
least 15 minutes
Temperature rises
above threshold when
the unit exits out of
dehumidistat mode
Error Code: “E7”
Fan off
Compressor off
8 Comm Error Communication from power
board is not being received
Valid communication
received from power
board
Error Code: “E8”
Power board continues to run unit.
UI board would not be able to
make changes to operation until
communication is restored.
20