WF080 Series
Nominal Capacity Rating: 8,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 100lbs (120/230VAC)
Model
Operating
Voltage
Range
(Volts)
Inrush
Current
(Start
Up
Current)
(Amps)
Loading
Current
(Running
Current)
(Amps)
SCCR
(Short
Circuit
Current
Rating)
(Amps)
Recommended
Fuse Selection
(Amps)
KVA Rating
(K-Watts)
Refrigerant
Type
Refrigerant
Amount
(ounces)
Low/High
Unit
Pressures
(psi)
WF080126
110-120
42.70
13.00
*2
25 Amp Class
CC, CCMR
Time Delay *
1.5
R422d
26.00
144 / 335
WF080236
220-240
24.20
7.10
*2
15 Amp Class
CC, CCMR
Time Delay *
1.5
R422d
26.00
144 / 335
* Time-delay Fuses with the following electrical characteristics are recommended. Fast -acting fuses
are not recommended.
% of Ampere Rating
Opening Time
110 %
15min Minimum
125 %
1hr Maximum
200 %
12sec Minimum
4min Maximum
*2
SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel /
enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.