Appendix C. Vendor Information – Thermal Solutions
NOTE:
All Modbus TCP/IP registers are the same as the Modbus RTU registers for the serial device. If
this point list is needed, contact Thermal Solutions technical support. The Modbus TCP/IP node
address of the device is also the same as the Modbus RTU node address.
RWF40 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks
Appendix C.1.
Point Name
BACnet
Object Type
BACnet
Object ID
N2 Data
Type
N2
Address
LonWorks Name
LonWorks SNVT
Com Status
BI
1
DI
1
nvoComStatus_XXX
SNVT_switch
Input 1
AI
1
AI
1
nvoInput1_XXX
SNVT_count_inc_f
Input 2
AI
2
AI
2
nvoInput2_XXX
SNVT_count_inc_f
Input 3
AI
3
AI
3
nvoInput3_XXX
SNVT_count_inc_f
First Setpoint
AV
4
AO
4
nvoFirstSP_XXX
SNVT_count_inc_f
Second Setpoint
AV
5
AO
5
nvoSecondSP_XXX
SNVT_count_inc_f
Operation Mode
AV
6
AO
6
nvoOpMode_XXX
SNVT_count_inc_f
Process Enable
BV
7
DO
7
nvi/nvoProcEnbl_XXX
SNVT_switch
Process Setpoint
AV
8
AO
8
nvi/nvoProcSP_XXX
SNVT_count_inc_f
Enable K1
BV
9
DO
9
nvi/nvoEnableK1_XXX
SNVT_switch
Enable K2
BV
10
DO
10
nvi/nvoEnableK2_XXX
SNVT_switch
Enable K3
BV
11
DO
11
nvi/nvoEnableK3_XXX
SNVT_switch
Enable K6
BV
12
DO
12
nvi/nvoEnableK6_XXX
SNVT_switch
Step Control
AV
13
AO
13
nvi/nvoStepCtrl_XXX
SNVT_count_inc_f
Modulation
AV
14
AO
14
nvi/nvoModulatn_XXX
SNVT_lev_percent