Thermal Solutions ProtoNode Start-up Guide
Page 11 of 47
3.4 Selecting the Desired Protocol Configuration
•
ProtoNode FPC-N34 BACnet units use the “S” bank of DIP switches (S0 – S3) to select the
protocol configuration.
o
See the table in
for the switch settings to select
o
The OFF position is when the DIP switches are set closest to the outside of the box
•
ProtoNode FPC-N35 LonWorks units do not use the “S” bank DIP switches (S0 – S3) to select a
field protocol.
o
On ProtoNode FPC-N35 units, these switches are disabled; the field protocol is always
LonWorks
ProtoNode FPC-N34
S Bank DIP Switches
Profile
S0
S1
S2
S3
BACnet/IP
Off
Off
Off
Off
BACnet MS/TP
On
Off
Off
Off
Metasys N2
Off
On
Off
Off
Modbus TCP/IP
On
On
Off
Off
BACnet MS/TP (single node)
Off
Off
On
Off
NOTE: When setting DIP switches, ensure that power to the board is OFF.
S0 – S3 DIP
Switches
S Bank DIP Switch Location
Profile Settings for ProtoNode
Figure 5: S Bank DIP Switches
S3
S2
S1
S0
Off
On