47
. Heating Boiler Piping Diagrams
(continued)
Figure 18: Multiple Boiler, Primary Reverse-Return Piping
System Pump
Air Vent
Expansion Tank
Pressure Reducing Valve
Full Port Isolation Valve
Y-Strainer
Check Valve
From System
To System
Motorized isolation Valve
Make Up Water
Factory Supplied Manifold
1. This is a suggested piping configuration. it is the
installer's responsibility to conform with local codes
and ordinances for additional requirements.
2. Pressure relief valve setting shall not exceed
pressure rating for any component in the system.
3. Boiler pump must be sized to overcome pressure
drop accross entire boiler loop.
NOTICE
NOTICE
1. These are suggested piping configurations. It is the installer's responsibility to
conform to local codes and ordinances for additional requirements.
2. Pressure relief valve rating shall not exceed pressure rating of any component
in the system.
3. Some piping components cannot be supported by the pipping. Refer to the
manufactures' installation instructions.
4. Circulation pump must be sized to overcome the pressure drop across the entire
loop.
!
System Circulator
Purge Valve
Air Vent
Isolation Valve
Factory Supplied Manifold
Check Valve
Pressure Reducing Valve
Isolation Valve
Expansion Tank
Differential Pressure Bypass
Y-Strainer
To System
Make Up Water
From System
Thermal Solutions Products LLC
Notes:
1. This is a suggested piping configuration. It is the
installer's responsibility to to conform to local codes
and ordinances for additional requirements.
2. Relief valve shall not exceed the pressure
rating of any components in the system.
3. The circulator shall be sized to overcome the
pressure drop across the entire loop.
8/30/2019
AMP Variable Primary Piping
Figure 19: Single Boiler, Variable Primary Piping