Thermal Gas Systems HALOGUARD II/IR Скачать руководство пользователя страница 6

 

   Rev.2.1  08/03/04 

6

INSTALLATION 

 

1.  Check power supply. (See Section “Before Installation 3a”) 

2.  Disconnect power before beginning. 

3.  Mounting Instructions 

a.  To mount Haloguard

 II/IR controller: 

1.  Install No. 10 x 1” screw at approximate center of desired location. Slip controller over 

fastener head.  

2.  Remove lower cover to expose lower circuit board.  Install two additional fasteners 

through holes provided beneath lower cover. 

b.  To mount IR Sensor Module

 

1.  Mount IR Module in a 

VERTICAL

 position in a location not subject to vibration or 

extreme temperature fluctuation.  Remove cover.  Secure with No. 8 x 1” (min.) screws 

through (4) holes beneath cover or use mounting feet provided. Extend sample tubing to 

18-24” above floor, terminate with end of line filter. 

2.  Inlet/Exhaust Extension (optional) may be used to extend sample point up to 200FT with 

0.125”OD x 0.093”ID nylon, copper, or stainless steel tubing.   When extending tubing: 

 

a.  Keep sample lines as short as possible and free of kinks. 

 

b. Attach 30 micron Inlet Filter at sample point. 

 

c.  Exhaust to atmosphere.  

DO NOT 

install any device which might restrict the flow. 

Refer to FIGURE 3 - Controller Lower Circuit Board before proceeding. 

DO NOT CUT SUPPLIED CABLE 

Maximum Extension length 1000 Feet. 

4.  Connecting Haloguard

 II/IR Controller and IR Sensor Module 

a. 

Wiring Instructions using supplied cable without extension

1.   Eight feet (8FT.) of cable with DIN connectors is supplied.  Connect cable from 

Haloguard

 II/IR Controller to IR Sensor Module location 

Refer to Figures 2 and 3 before proceeding.

 

b. 

Wiring Instructions using cable with extension

 

1.

We recommend 3 conductor 18 ga. cable with foil shield, Carol C0455 or equal.  Use 3/4” 

conduit if required

.  

 

.  2. Haloguard

 II/IR Controller is provided with 18” cable with DIN Connector and IR 

module is provided with 6 

1/2

’ cable. To extend sensor beyond the provided length, remove 

18” cable with DIN connector from controller Lower Circuit Board. Splice or solder 

extension cable to end of 18” cable.  Reconnect extended sensor cable to terminal block in 

lower circuit board of controller.  

 

 

Terminal 

Provided 

Wire Color 

Extension 

Wire Color 

 

Function 

T1 

Red 

Red 

See Note 

T2 

White 

White 

Signal 

T3 

Blk./Blk 

Black/Shield 

Ground 

 

 

Note: T1 Used with Oxygen Sensors Only. 

 

Figure 6 - Sensor Cable Terminal Connection

 

 

 

 

Содержание HALOGUARD II/IR

Страница 1: ...r 0 10 VDC G R 123 H Oxygen Options Accessories A Audible Alarm B UPS C Auto Calibration E Inlet Exhaust Extension L Strobe Light T TW A Integration 11285 Elkins Road Bldg H 1 Roswell GA 30077 TEL 770...

Страница 2: ...Calibration 9 5 Testing 10 6 Trouble Shooting 10 7 Specifications 11 FIGURES Page 1 Dimension Drawing 4 2 Haloguard II IR Controller Upper Circuit Board 5 3 Haloguard II IR Controller Lower Circuit B...

Страница 3: ...urce of 115 230 VAC 50 60 Hz single phase circuit rated 15A minimum for both Haloguard II IR Controller and IR Sensor Module b IR Sensor Module should be mounted near potential leaks in a quiet area o...

Страница 4: ...scale c OFFSCALE LED and Relay Factory set at 1000ppm See Figure 11 d HI Alarm LED LO Alarm LED and Relays User adjustable 10ppm to 1000ppm See Figure 8 Note Optional TWA Integration activates LOW Ala...

Страница 5: ...ans Auto Scan Mode Gas Type R 11 R 12 R 123 R 134 O2 etc Sensor Type CMOS Halocarbon NH3 Infrared Halocarbons Chemical O2 Alarm Messages LO ALARM TWA ALARM HI ALARM OFFSCALE FAULT Figure 5 LCD Display...

Страница 6: ...tmosphere DO NOT install any device which might restrict the flow Refer to FIGURE 3 Controller Lower Circuit Board before proceeding DO NOT CUT SUPPLIED CABLE Maximum Extension length 1000 Feet 4 Conn...

Страница 7: ...l Adjust potentiometer to the left of each screw terminal with screwdriver until it reads 4 975 VDC THIS SET UP MUST BE COMPLETED FOR EACH IR MODULE 1 thru 6 Sequence to subsequent active channels usi...

Страница 8: ...on Upper Circuit Board Figure 2 Select required settings from the following menu JP HALOGUARD II IR CONTROLLER FUNCTIONS JP 1 In house ONLY JP 2 Optional Autocalibration See 7a JP 3 Set scan rate 0 1...

Страница 9: ...s corrected f Audible Alarm Jumper on JP 9 is factory installed to activate alarm circuit To disable alarm remove JP 9 jumper WARNING ANALOG OUTPUT IS A DRIVEN SIGNAL DO NOT CONNECT ANY WIRE WITH VOLT...

Страница 10: ...ayed PPM value drops then Haloguard II IR is detecting the gas of interest or a gas that absorbs IR light at the same frequency LCD should display 0 ppm If LCD does not show 0 ppm follow calibration p...

Страница 11: ...se Time 1 Minute per sample point Operating Conditions IR Module 40o F to 120o F Non condensing O2 Sensor 40o F to 110o F Non condensing Controller 0o F to 120o F Non condensing Fault Diagnostics Indi...

Отзывы: