SPECIFICATIONS 

 

Technology: 

Infrared Photoacoustic  

 

 

 

Oxygen - Electro Chemical 

 

Electrical Supply:  115-230 VAC, 50-60Hz 

 

Output Signal: 

Std.  4 x  3A Dry Contact Relays  

 

(NO or NC) 

 

Opt.  4 x 0 - 5 VDC Analog 

 

Alarm Outputs: 

Three Level Contact Closure 

 

Readout: 

Digital Meter, Displayed in PPM 

 

Gas Type, Range and options. 

 

Display Accuracy:  1 ppm    0 - 100 ppm Range (IR) 

 

10 ppm 100 - 1000 ppm Range (IR) 

 

 

 

1%  Electrochemical (Oxygen) 

 

Ranges: 

0 - 1000 ppm    R11, R12, R22, 

 

R134a, R113, and R123,  

 

 

 

0 - 25% Oxygen 

Response Time: 

< 1 Minute per sample point 

 

Operating Conditions: 

  IR Module 

+40

o

F to +120

o

F Non-condensing 

  O

2

 Sensor 

+40

o

F to +110

o

F Non-condensing 

  Controller 

 0

o

F to +120

o

F Non-condensing 

 

Fault Diagnostics:  Indicator Light or LCD Readout  

   

for fault diagnostics (See Fig.. 5)  

Materials: 

  IR Module 

NEMA 4/12/13 Design 

  Controller 

NEMA 12/13, IP65 Design 

  Oxygen Sensor  PVC and porous PP 

 

Weight: 

  IR Module 

10 lbs. 

  Controller: 

4 lbs. (Add 2 lbs. optional battery) 

 

Dimensions: 

  IR Module 

6-1/2” W x 14-1/4” H x 4” D 

  Controller 

10-1/2” W x 7-1/8” H x 4-1/4”D 

 

 

 

Initial factory settings are: 

Channel 

Calibration 

Gas 

 

 

 

 

 

 

Sensor 

Type 

 

 

 

 

 

 

 

Lo Alarm 

 

 

 

 

 

 

 

Hi Alarm 

 

 

 

 

 

 

Full Scale 

PPM 

 

 

 

 

 

 

TWA Alarm 

Level 

 

 

 

 

 

 

 

Figure 11 - Initial Factory Settings 

Содержание HALOGUARD II/IR

Страница 1: ...r 0 10 VDC G R 123 H Oxygen Options Accessories A Audible Alarm B UPS C Auto Calibration E Inlet Exhaust Extension L Strobe Light T TW A Integration 11285 Elkins Road Bldg H 1 Roswell GA 30077 TEL 770...

Страница 2: ...Calibration 9 5 Testing 10 6 Trouble Shooting 10 7 Specifications 11 FIGURES Page 1 Dimension Drawing 4 2 Haloguard II IR Controller Upper Circuit Board 5 3 Haloguard II IR Controller Lower Circuit B...

Страница 3: ...urce of 115 230 VAC 50 60 Hz single phase circuit rated 15A minimum for both Haloguard II IR Controller and IR Sensor Module b IR Sensor Module should be mounted near potential leaks in a quiet area o...

Страница 4: ...scale c OFFSCALE LED and Relay Factory set at 1000ppm See Figure 11 d HI Alarm LED LO Alarm LED and Relays User adjustable 10ppm to 1000ppm See Figure 8 Note Optional TWA Integration activates LOW Ala...

Страница 5: ...ans Auto Scan Mode Gas Type R 11 R 12 R 123 R 134 O2 etc Sensor Type CMOS Halocarbon NH3 Infrared Halocarbons Chemical O2 Alarm Messages LO ALARM TWA ALARM HI ALARM OFFSCALE FAULT Figure 5 LCD Display...

Страница 6: ...tmosphere DO NOT install any device which might restrict the flow Refer to FIGURE 3 Controller Lower Circuit Board before proceeding DO NOT CUT SUPPLIED CABLE Maximum Extension length 1000 Feet 4 Conn...

Страница 7: ...l Adjust potentiometer to the left of each screw terminal with screwdriver until it reads 4 975 VDC THIS SET UP MUST BE COMPLETED FOR EACH IR MODULE 1 thru 6 Sequence to subsequent active channels usi...

Страница 8: ...on Upper Circuit Board Figure 2 Select required settings from the following menu JP HALOGUARD II IR CONTROLLER FUNCTIONS JP 1 In house ONLY JP 2 Optional Autocalibration See 7a JP 3 Set scan rate 0 1...

Страница 9: ...s corrected f Audible Alarm Jumper on JP 9 is factory installed to activate alarm circuit To disable alarm remove JP 9 jumper WARNING ANALOG OUTPUT IS A DRIVEN SIGNAL DO NOT CONNECT ANY WIRE WITH VOLT...

Страница 10: ...ayed PPM value drops then Haloguard II IR is detecting the gas of interest or a gas that absorbs IR light at the same frequency LCD should display 0 ppm If LCD does not show 0 ppm follow calibration p...

Страница 11: ...se Time 1 Minute per sample point Operating Conditions IR Module 40o F to 120o F Non condensing O2 Sensor 40o F to 110o F Non condensing Controller 0o F to 120o F Non condensing Fault Diagnostics Indi...

Отзывы: