Thermal Gas Systems HALOGUARD II/IR Скачать руководство пользователя страница 2

 

 

                                     2                                                          Rev.2  07/26/98 

IMPORTANT 

READ ENTIRE BOOKLET BEFORE 

INSTALLING OR OPERATING 

HALOGUARD

TM

 II/IR MONITOR 

 

 

 

 

 

TABLE OF CONTENTS 

 

 

 

   

 

 

 

 

 

Page 

1.  Unpacking Instructions 

2.  Before Installation 

3.  Installation 

 

a.  Standard Cable Installation 

 

b.  Extended Cable Installation 

4.  Calibration 

 9 

5.  Testing 

10 

6.  Trouble Shooting 

10 

7.  Specifications 

11 

 

 

FIGURES 

 

   

 

 

 

 

 

Page 

1.  Dimension Drawing 

2.  Haloguard

 II/IR Controller Upper Circuit Board 

3.  Haloguard

 II/IR Controller Lower Circuit Board 

4.  Relay Junction Box Connections 

5.  LCD Display Features 

6.  Sensor Cable Terminal Connectors 

7.  IR Module Circuit Board 

8.  Alarm Jumper Settings 

9.  Exposure Limits 

10. Function Jumper Settings 

11. Initial Factory Settings 

11 

12. Wiring Diagram 

12 

   

   

 

 

Содержание HALOGUARD II/IR

Страница 1: ...r 0 10 VDC G R 123 H Oxygen Options Accessories A Audible Alarm B UPS C Auto Calibration E Inlet Exhaust Extension L Strobe Light T TW A Integration 11285 Elkins Road Bldg H 1 Roswell GA 30077 TEL 770...

Страница 2: ...Calibration 9 5 Testing 10 6 Trouble Shooting 10 7 Specifications 11 FIGURES Page 1 Dimension Drawing 4 2 Haloguard II IR Controller Upper Circuit Board 5 3 Haloguard II IR Controller Lower Circuit B...

Страница 3: ...urce of 115 230 VAC 50 60 Hz single phase circuit rated 15A minimum for both Haloguard II IR Controller and IR Sensor Module b IR Sensor Module should be mounted near potential leaks in a quiet area o...

Страница 4: ...scale c OFFSCALE LED and Relay Factory set at 1000ppm See Figure 11 d HI Alarm LED LO Alarm LED and Relays User adjustable 10ppm to 1000ppm See Figure 8 Note Optional TWA Integration activates LOW Ala...

Страница 5: ...ans Auto Scan Mode Gas Type R 11 R 12 R 123 R 134 O2 etc Sensor Type CMOS Halocarbon NH3 Infrared Halocarbons Chemical O2 Alarm Messages LO ALARM TWA ALARM HI ALARM OFFSCALE FAULT Figure 5 LCD Display...

Страница 6: ...tmosphere DO NOT install any device which might restrict the flow Refer to FIGURE 3 Controller Lower Circuit Board before proceeding DO NOT CUT SUPPLIED CABLE Maximum Extension length 1000 Feet 4 Conn...

Страница 7: ...l Adjust potentiometer to the left of each screw terminal with screwdriver until it reads 4 975 VDC THIS SET UP MUST BE COMPLETED FOR EACH IR MODULE 1 thru 6 Sequence to subsequent active channels usi...

Страница 8: ...on Upper Circuit Board Figure 2 Select required settings from the following menu JP HALOGUARD II IR CONTROLLER FUNCTIONS JP 1 In house ONLY JP 2 Optional Autocalibration See 7a JP 3 Set scan rate 0 1...

Страница 9: ...s corrected f Audible Alarm Jumper on JP 9 is factory installed to activate alarm circuit To disable alarm remove JP 9 jumper WARNING ANALOG OUTPUT IS A DRIVEN SIGNAL DO NOT CONNECT ANY WIRE WITH VOLT...

Страница 10: ...ayed PPM value drops then Haloguard II IR is detecting the gas of interest or a gas that absorbs IR light at the same frequency LCD should display 0 ppm If LCD does not show 0 ppm follow calibration p...

Страница 11: ...se Time 1 Minute per sample point Operating Conditions IR Module 40o F to 120o F Non condensing O2 Sensor 40o F to 110o F Non condensing Controller 0o F to 120o F Non condensing Fault Diagnostics Indi...

Отзывы: