Thermal Edge CS011-D48 Series Скачать руководство пользователя страница 24

                                                                                                      

 

1800 Hurd Drive ● Irving, Texas 75038 ● (972) 580-0200 ● (888) 580-0202 ● Fax (972) 580-0277 

URL:  www.thermal-edge.com ● Email:  

[email protected]

 

SP-ENG-211-D48-02 Rev 2.3          24 | 

P a g e

                                                                                   

Warranty Information

 

Thermal Edge products are warranted to be free of defects in workmanship, materials and components. The warranty 
period applies from date of shipment for five years.  Replacement components have a one year warranty period, 
except for hermetic system components, which have a 90 day warranty period. 

The above warranty applies when the equipment is operated under the following conditions:  

 

Ambient temperature not in excess of performance rating in normal atmosphere or as stated on product 
nameplate 

 

Voltage variation within limits stated in User & Technical Manual 

 

Frequency variation no greater than ± 3Hz from nameplate rating 

 

Maximum cooling load no higher than air conditioner nameplate rating  

 

Waiting five minutes before restarting air conditioner after intentional or acciden tal shutoff 

 

Compliance to all other installation, maintenance and operating instructions, as supplied  

Thermal Edge cannot assume responsibility for misapplication of its products or the erroneous selection of an 
inappropriate product by a non-authorized Thermal Edge representative. Our applications engineers will gladly assist 
in the selection of the proper product provided all required details of the application are furnished.  

Thermal Edge assumes no liability beyond the repair or replacement of its own pr oduct. This Warranty does not 
cover: 

 

Labor or reimbursement of labor for evaluation, removal, installation, repair, or cost of any warranted part, 
except at the Thermal Edge factory in Dallas, Texas 

 

Use of equipment for other than its designed purpose or operating conditions 

 

Operation in harsh, oily, corrosive or other abnormal environmental conditions, without the proper filtration, 
sealing, protective coatings and/or weather protection, or cosmetic corrosion that does not affect operation  

 

Damage to hermetic system resulting from continuous operation with dirty or clogged air filters or improper 
or negligent maintenance 

 

Use of refrigerant other than designated 

 

Customer modification or abuse 

 

Shipping damage or other accident 

 

Repair or service by unauthorized personnel. 

Thermal Edge must be notified of a claim in writing not later than fourteen (14) days from the date when buyer has 
become aware of such occurrence, or immediately, when the defect is such that it may cause damage.  

If air conditioner is to be shipped or transported at any time, it is best to pack in original packaging and strap to pallet 
to prevent damage.  Air conditioner must be kept upright at all times.  Air conditioners  that have internal damage due 
to shipping are not covered under the Warranty.  Claims for shipping damage are the responsibility of the Consignee.  
Damage must be noted on Bill of Lading at time of receipt. Timely claims must be filed with the freight carrier.  

The purchaser assumes the responsibility of grounding the unit and  installing it in accordance with local electrical and 
safety codes, as well as the 2008 National Electric Code (NEC) and OSHA.  

THIS WARRANTY CONSTITUTES THE ENTIRE WARRANTY WITH RESPECT TO THE PRODUCT AND IS IN LIEU 
OF ALL OTHERS, EXPRESSED OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY AND 
WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND IN NO EVENT IS THERMAL EDGE 
RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER.

 

 

Содержание CS011-D48 Series

Страница 1: ...User Technical Manual CS011 D48 Series Rev 2 3...

Страница 2: ...Slotnick Updated warranty 2 0 02 19 2019 B Slotnick Updated mounting instructions alarm settings RMA procedure 2 1 06 18 2019 B Slotnick Updated preliminary testing instructions compressor protection...

Страница 3: ...4 Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller Programmi...

Страница 4: ...ecting the Equipment Thermal Edge air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect y...

Страница 5: ...to record the data from the label to the template below and keep this information in a safe place for warranty and ordering parts To prevent damage to equipment electrical panel and wiring and to pre...

Страница 6: ...e that the electric power is protected by a circuit protection device refer to the Unit Specification section in this manual for proper circuit protection sizing Connect a power source to the air cond...

Страница 7: ...t to let any cutting debris fall into the enclosure Hang the air conditioner on the easy hang flange and from inside the enclosure use the fasteners supplied to attach the air conditioner to the enclo...

Страница 8: ...mum Ambient 125 F Unit Weight 30 lbs 120VAC Model Operating Voltage Range Volts Loading Current Running Current Amps SCCR Short Circuit Current Rating Amps Recommended Fuse Selection Amps KVA Rating R...

Страница 9: ...Hurd Drive Irving Texas 75038 972 580 0200 888 580 0202 Fax 972 580 0277 URL www thermal edge com Email support thermal edge com SP ENG 211 D48 02 Rev 2 3 9 P a g e THIS PAGE IS INTENTIONALLY LEFT BL...

Страница 10: ...oint Default Settings 105 F Dry Contact High Temperature Alarm Set Point 2 F Recovery Differential 3min Temperature Alarm Delay At the default settings the Dry Contact initial conditions are normally...

Страница 11: ...the Digital Temperature Controller Programming section for details on all default settings Open Door Kill Switch This option provides you with an adjustable and mountable safety switch for your elect...

Страница 12: ...e presence of corrosive chemicals such as hydrogen sulfide chlorine etc Condenser and evaporator coils are available with electrostatically applied epoxy coating to prevent corrosion Three options are...

Страница 13: ...2 minute time delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is on but is not flashing and the compressor is not running an internal fault...

Страница 14: ...value 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without pressing a k...

Страница 15: ...n Alarm Only 2 HA2 Condenser High Temperature Alarm P2 153 F for 3 minutes Compressor turned Off by pressure switch if temperature continues to rise 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3...

Страница 16: ...and attached by plug in connections Compressor Thermal Edge uses hermetically factory sealed compressors that are quiet low vibration and are maintenance free Thermal overload devices are installed to...

Страница 17: ...mperature Probe Mounting Clip 52126 250C Thermal Expansion Value TXV 32023 1 Compressor 31659 1 Gasket Installation Kit 71410 CS01 Evaporator Fan 41002 2 1 Condenser Fan 41002 2 1 Note Qty 2 Safety In...

Страница 18: ...on position ON OFF Toggle Switch then Retry Verify input power meets voltage requirements as shown in the UL label YES If problem is still present contact technical support Unit Overheats Insufficient...

Страница 19: ...ssor Use meter3 Check for faulty evaporator fan3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Is compressor...

Страница 20: ...ind controller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer t...

Страница 21: ...g e Physical Dimensions Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed against...

Страница 22: ...Hurd Drive Irving Texas 75038 972 580 0200 888 580 0202 Fax 972 580 0277 URL www thermal edge com Email support thermal edge com SP ENG 211 D48 02 Rev 2 3 22 P a g e THIS PAGE IS INTENTIONALLY LEFT B...

Страница 23: ...al edge com SP ENG 211 D48 02 Rev 2 3 23 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided in t...

Страница 24: ...art except at the Thermal Edge factory in Dallas Texas Use of equipment for other than its designed purpose or operating conditions Operation in harsh oily corrosive or other abnormal environmental co...

Страница 25: ...Number Serial Number Customer name and contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available Air Cond...

Страница 26: ...om the left connect the wires by inserting them into the lower receptacles located on the front of connector in the following order NOTE If using stranded wires it may be difficult to insert into the...

Отзывы: