Table 12 - Air Cooled Chiller Electrical Data (60 Hz) - continued
Model
Process
Pump
Size
Rated
Voltage
Allowable
Power
Compressor Data
Condenser Fan Data Pump
Data
Unit Data
Comp 1
Comp 2
Fan 1 Fan 2 Fan 2
Min Max RLA
1
LRA
2
RLA
1
LRA
2
FLA
3
FLA
3
FLA
3
FLA
3
MCA
4
MOP
5
NQA15
None
230/3/60 207 253
55.8 340.0
-
-
8.3
-
-
0.0
80.6
136.4
3 HP
230/3/60 207 253
55.8 340.0
-
-
8.3
-
-
9.6
90.2
146.0
5 HP
230/3/60 207 253
55.8 340.0
-
-
8.3
-
-
15.2
95.8
151.6
7.5 HP 230/3/60 207 253
55.8 340.0
-
-
8.3
-
-
22.0 102.6 158.4
None
460/3/60 414 506
26.9 173.0
-
-
4.6
-
-
0.0
39.5
66.4
3 HP
460/3/60 414 506
26.9 173.0
-
-
4.6
-
-
4.8
44.3
71.2
5 HP
460/3/60 414 506
26.9 173.0
-
-
4.6
-
-
7.6
47.1
74.0
7.5 HP 460/3/60 414 506
26.9 173.0
-
-
4.6
-
-
11.0
50.5
77.4
None
575/3/60 518 633
23.7 132.0
-
-
3.7
-
-
0.0
34.3
58.0
3 HP
575/3/60 518 633
23.7 132.0
-
-
3.7
-
-
3.8
38.1
61.8
5 HP
575/3/60 518 633
23.7 132.0
-
-
3.7
-
-
6.1
40.3
64.0
7.5 HP 575/3/60 518 633
23.7 132.0
-
-
3.7
-
-
8.8
43.1
66.8
NQA20
None
230/3/60 207 253
33.3 239.0 33.3 239.0
8.3
8.3
-
0.0
94.0
127.3
3 HP
230/3/60 207 253
33.3 239.0 33.3 239.0
8.3
8.3
-
9.6
103.6 136.9
5 HP
230/3/60 207 253
33.3 239.0 33.3 239.0
8.3
8.3
-
15.2 109.2 142.5
7.5 HP 230/3/60 207 253
33.3 239.0 33.3 239.0
8.3
8.3
-
22.0 116.0 149.3
10 HP 230/3/60 207 253
33.3 239.0 33.3 239.0
8.3
8.3
-
28.0 122.0 155.3
None
460/3/60 414 506
17.9 125.0 17.9 125.0
4.6
4.6
-
0.0
50.7
68.6
3 HP
460/3/60 414 506
17.9 125.0 17.9 125.0
4.6
4.6
-
4.8
55.5
73.4
5 HP
460/3/60 414 506
17.9 125.0 17.9 125.0
4.6
4.6
-
7.6
58.3
76.2
7.5 HP 460/3/60 414 506
17.9 125.0 17.9 125.0
4.6
4.6
-
11.0
61.7
79.6
10 HP 460/3/60 414 506
17.9 125.0 17.9 125.0
4.6
4.6
-
14.0
64.7
82.6
None
575/3/60 518 633
12.8
80.0
12.8
80.0
3.7
3.7
-
0.0
37.1
49.9
3 HP
575/3/60 518 633
12.8
80.0
12.8
80.0
3.7
3.7
-
3.8
41.0
53.8
5 HP
575/3/60 518 633
12.8
80.0
12.8
80.0
3.7
3.7
-
6.1
43.2
56.0
7.5 HP 575/3/60 518 633
12.8
80.0
12.8
80.0
3.7
3.7
-
8.8
45.9
58.7
10 HP 575/3/60 518 633
12.8
80.0
12.8
80.0
3.7
3.7
-
11.2
48.3
61.1
1
RLA is Rated Load Amps.
2
LRA is Locked Rotor Amps.
3
FLA is Full Load Amps.
4
MCA is Minimum Circuit Amps (for wire sizing), complies with NEC, Section 430-24.
5
MOPD is Maximum Over-current Protection Device, complies with NEC, Section 430-53.