4
Table 3 – Remote Air Cooled Condenser Chiller General Data (60 Hz)
Model
NQR05 NQR08 NQR10 NQR15 NQR20
NQR25
NQR30
NQR35
NQR40
Cooling Capacity (tons)
1
5.3
7.6
11.0
15.3
20.8
25.8
30.7
35.5
39.9
Set Point Range (°F)
20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80 20 to 80
Refrigerant
R410A R410A R410A R410A R410A R410A R410A R410A R410A
Sound Pressure @ 1 meter (dBA)
2
69.8
70.3
71.3
73.3
73.7
73.7
74.7
76.6
78.1
Minimum Unloaded Capacity (tons)
1.2
1.8
2.7
3.6
4.8
6.0
7.2
8.4
9.6
Pump Motor Size (hp)
1.5
1.5
1.5
3
3
5
5
5
5
Pump Flow (gpm)
13
18
27
36
48
61
73
83
92
Net Available Pump Pressure (psi)
3
35
36
30
48
39
57
54
53
50
Unit MCA @ 460/3/60 (amps)
4
16.4
22.6
27.4
39.7
46.3
60.8
69.3
73.7
77.2
Length (inches)
48
75
75
75
87
87
105
105
105
Width (inches)
35
35
35
35
41
41
41
41
41
Height (inches)
54
54
54
54
47
47
47
47
47
Reservoir Holding Capacity (gal)
11
22
22
22
50
50
67
67
67
Process Connections (inches)
1.5
1.5
1.5
1.5
2
2
2
2.5
2.5
Refrigerant Liquid Line (inches)
0.625
0.625
0.875
0.875
0.875
1.125
1.125
1.375
1.375
Refrigerant Suction Line (inches)
0.625
0.625
0.875
0.875
0.875
1.125
1.125
1.375
1.375
Shipping Weight (lbs)
720
1,195
1,195
1,315
1,900
2,100
2,250
3,400
3,900
1
Cooling tons based on 12,000 BTU/Hr/ton with 50°F leaving coolant and 95°F ambient air.
2
Sound pressure is for chiller unit only; see the Remote Air-Cooled Condenser table for condenser sound pressures.
3
Net available pressure at outlet of chiller is pump discharge pressure less the internal coolant-circuit pressure loss.
4
MCA is Minimum Circuit Amps (for wire sizing), complies with NEC, Section 430-24.
Table 4 – Remote Air-Cooled Condenser General Data (60 Hz)
Condenser
Model
Chiller
Used
With
Dimensions (in)
Weights (Lbs)
Total Air
Flow
(cfm)
Sound
Pressure
(dBA)
1
MCA @
460/3/60
(amps)
2
Refrigerant
Connections (in)
L
W
H
Ship
Oper
Inlet
Outlet
KCM009
NQR05 53.625 43.625 48.125
245
Operating
weight
varies
based on
system
charge
and
operating
conditions
6,870
60
1.4
0.875
1.125
KCM011
NQR08 53.625 43.625 48.125
265
6,620
60
1.4
0.875
1.125
KCM014
NQR10 93.625 43.625 48.125
415
14,400
62
2.6
1.375
1.125
KCL023
NQR15 125.750 45.625 54.000
670
24,000
72
7.0
2.125
1.375
KCL030
NQR20 125.750 45.625 54.000
720
22,600
72
7.0
2.125
1.625
KCL037
NQR25 125.750 45.625 54.000
800
20,600
72
7.0
2.125
1.625
KCL045
NQR30 180.750 45.625 54.000
1,075
33,900
73
10.1
2.625
1.625
KCL054
NQR35 180.750 45.625 54.000
1,175
32,000
73
10.1
2.625
2.125
KCL056
NQR40 180.750 45.625 54.000
1,200
30,900
73
10.1
2.625
2.125
1
Sound pressure at 3 meters.
2
MCA is minimum circuit amps (for wire sizing) as provided by the remote condenser manufacturer.