Big Dipper

®

 AST System Series

Troubleshooting

Big Dipper unit overflows

(1) Check to see that the outlet pipe is not reduced to a 

smaller size, the outlet piping is vented, has as few 90 

degree outlet turns as possible, and that no “P” trap is 

installed on the outlet.  Re-plumb the piping, if necessary.  

Check outlet piping for clogs.  Have a plumber clean the 

line, if necessary.

2) Make sure that the solids collection chamber is free 

of excessive debris.  To check Eductor Pump operation, 

unplug the unit for 10 seconds, then re-renergize.  The 

Eductor Pump should automatically activate. 

 

3) Check the bottom of the grease chamber for excessive 

solids and silt buildup which may be blocking the outlet 

baffle.  Disconnect the power and use a long handled 

spatula or similar instrument to stir the bottom while water 

flows through the unit.  If necessary, drain and clean the 

sediment from the unit.  To prevent recurrence, schedule 

this cleaning to be done on a regular basis (properly used, 

a wet vac may be appropriate for cleaning sediment from 

the bottom of the unit).

4) Make sure the flow rate to the unit does not exceed the 

maximum flow rate, which is shown on the nameplate.  If 

necessary, have a plumber install an approved flow control 

to restrict the inlet flow to the specified level or install a 

properly sized Big Dipper for the application.

Excessive water observed in the grease

collection container

1) Check Timer for excessive “on” time.  Unit will pick up 

incidental water after all grease is removed.

2) Make sure that the water flow to the unit does not 

exceed the rated flow and there are no drain line clogs 

downstream from the unit.

No grease is collected in the container

(1) Check to be sure the power is on and the time control 

is set correctly.  The “on” time should be no less than 

15 minutes per day.  

  There is a Power Indicator Light 

under the Timer which indicates that Power is reaching 

the unit.  If this light is not Red, power is not reaching 

the unit.

 

(2)  Remove  the  lid  and  clean  away  any  buildup  that 

may be present on the wiper blades or collection trough.  

Make sure the wiper blade(s) are properly in place on 

the skimmer wheels.  Replace wiper blades when worn 

or warped.

(3) Press the Jog Switch button on the side of the center 

module to ensure that the skimming wheel turns.  CAU-

TION: Keep your hands away from moving parts to avoid 

possible injury.  If the skimmer motor does not come on, 

the motor assembly must be replaced.

(4) Check for congealed grease in the unit.  If the Big 

Dipper’s  heating  element  is  not  warming  the  unit,  the 

heating element must be replaced.

(5) Some sites do not generate enough grease to be cap-

tured by the skimming process.  Set Timer for minimum 

operation - 1 Tab (15 Min.)

Objectionable odor

(1) Make sure grease/oil is being skimmed properly from 

the unit.

(2)  Check  the  timer  settings  for  excessive  “on”  time.  

Also check to see if any water is collected in the grease 

collector.  Reduce operating time until water is no longer 

observed in the grease collector.

(3) If excessive sediment has collected on the bottom 

of the unit, clean the unit as described in item 3 in “Big 

Dipper unit overflows.”

(4) Clean the solids strainer assembly and grease collec-

tion container more frequently.

(5) Grease interceptors, grease traps, automatic recovery 

units, grease removal devices and other similar plumbing 

devices receiving kitchen flows from sinks, floor drains, 

woks and other food bearing sources may generate odors.  

There are many factors influencing odor evolution and 

dissemination.  These include room ventilation, kitchen 

menu, ambient temperatures, ware washing practices, 

grease/oil input, daily input fluid volume, sanitizers, instal-

lation plumbing design and product maintenance/upkeep.  

Odors are usually prevented by good area ventilation, 

frequent  fluid  inputs,  good  product  maintenance  prac-

tices and proper product installation.  Additional steps, 

including aeration, chlorination, improved area ventilation 

and additional maintenance control, may be needed at 

some sites.

Содержание Big Dipper W-1250-AST

Страница 1: ...51 F 336 626 5739 E mail info thermaco com Online www big dipper com Installation Operation Instructions For Big Dipper W 750 AST and W 1250 AST Automatic Solids Transfer AST Series Units Including 23...

Страница 2: ...000 2 Table of Contents Table of Contents AST System Overview 3 AST System Maintenance 5 AST Timer Operation 6 AST System Troubleshooting 7 How To Reverse AST System Operation 8 Plumbing Installation...

Страница 3: ...kimming wheel at a user set time Only the cleaned water exits the unit and flows into the facility drain lines Incidental food solids less than 1 5 38 mm in diameter are separated and flushed out of t...

Страница 4: ...mer on the unit is no longer operating and should be replaced If pressing the button does nothing then there may be a problem with the motor assembly Please contact Thermaco or your local service agen...

Страница 5: ...cumulated solids Be sure to spray down both the inside and outside surfaces of the strainer assembly E Check the thickness of the grease layer at the top of the unit If there is more than a 1 2 12 mm...

Страница 6: ...r unit needs to be set for the proper automatic self cleaning operation for the facility The Big Dipper W 750 AST model is equipped with one 1 24 Hour 96 Event time controller while the W 1250 AST mod...

Страница 7: ...5 minutes per day There is a Power Indicator Light under the Timer which indicates that Power is reaching the unit If this light is not Red power is not reaching the unit 2 Remove the lid and clean aw...

Страница 8: ...UNPLUG UNIT BEFORE REMOVING LID SYSTEM WILL NOT OPERATE UNLESS CENTER LID LATCHES ARE FASTENED Note W 750 AST has one 1 module W 1250 AST has two 2 modules 1 Unlatch the Unit lid Pull the side wings o...

Страница 9: ...ope of 1 4 per foot 2cm per meter Use only sweep connections Don t reduce the pipe sizing on the outlet piping Don t install P trap on outlet connection of system Note The system already has a interna...

Страница 10: ...ht Greater Than 6 feet 1 95m For installations where there is a significant amount of head height More than 6 ft 1 95 m Thermaco Inc recommends installation of the optional VFCA Vented Flow Control mo...

Страница 11: ...controlled by a ground fault circuit breaker There is a Power Indicator Light that will glow Red if power is being fed to the unit If this light is off power is not reaching the unit This Big Dipper...

Страница 12: ...CK CONNECTOR FULLY INSULATED FEMALE CONNECTOR BLACK RED RED INTERCHANGE FULLY INSULATED QUICK CONNECTORS TO CHANGE HEATER OPERATING MODE RED WIRE TO THERMOSTAT GIVES SIMULTANEOUS HEATER MOTOR OPERATIO...

Страница 13: ...N WHITE BLACK WHITE WHITE BLACK BLACK WHITE WHITE WHITE POWER SUPPLY CORD BLACK BLACK FULLY INSULATED QUICK CONNECT PIGGY BACK CONNECTOR FULLY INSULATED FEMALE CONNECTOR BLACK RED RED INTERCHANGE FULL...

Страница 14: ...ensboro St Asheboro N C 27204 2548 Phone 336 629 4651 MNL ASTCU14000 14 Big Dipper AST System Wiring Diagram Junction Box Wiring Diagram For Big Dipper Model W 1250 AST POWER RING TERMINALS TO GROUND...

Страница 15: ...sheboro N C 27204 2548 Phone 336 629 4651 MNL ASTCU14000 15 Big Dipper AST System Electrical Components Safety Switch Part MSS 7 Motor Part M 58 Heater Part H 8 Thermostat Part TSTAT 4 Power Indicator...

Страница 16: ...el Wiper Assembly Part WWA 4 Skimming Wheel Assembly Part PDA 3 Wheel Drive Sprocket Part WDS 3 Big Dipper AST Lid Components With Wheel Cover Removed Wiper Blades 2 Part PB 3 Inlet Outlet Safety Swit...

Страница 17: ...itch Part ESHS 1 Big Dipper AST System Component Identification Big Dipper AST System Component Identification Rear Electrical Enclosure Assembly Part REEA 1 Timer Cover Part MTC 1 Wheel Cover Part MS...

Страница 18: ...125 FOR W 1250 AST LID GASKET PART RG 7 WIPER BLADES PART PB 3 W 750 AST requires two 2 W 1250 AST requires four 4 WHEEL WIPER ASSEMBLY PART WWA 4 WHEEL DRIVE SPROCKET PART WDS 3 SKIMMING WHEEL ASSEMB...

Страница 19: ...s Thermaco shall not be respon sible for damage to products resulting from vault flooding sewer line back up pumping or lift station failure ambient water flow or other sources of water damage This wa...

Отзывы: