AIR FOR COMBUSTION AND VENTILATION

 

 

WARNING

: This heater shall not be 

installed in a confined space or unusually 

tight construction unless provisions are provided 
for adequate combustion and ventilation air. 
Read the following instructions to ensure proper 
fresh air for this and other fuel-burning 
appliances in your home. 
 

Providing Adequate Ventilation 

 
This heater shall not be installed in a room or 
space unless the required volume of indoor 
combustion air is provided by the method 
described in the NATIONAL FUEL GAS CODE, 
ANSI Z223.1/NFPA 54, the INTERNATIONAL 
FUEL GAS CODE, or applicable local codes. 
The following are excerpts from National Fuel 
Gas Code, ANSI Z223.1/ NFPA 54. Air for 
Combustion and Ventilation. All spaces in homes 
fall into one of the three following ventilation 
classifications: 
1. Unusually Tight Construction 
2. Unconfined Space 
3. Confined Space 
   
The information on the following pages will help 
you classify your space and provide adequate 
ventilation. 
 

Confined and Unconfined Space 

 
The National Fuel Gas Code, ANSI 
Z223 .1/NFPA 54 defines a confined space as a 
space whose volume is less than 50 cu. ft. per 
1,000 BTU/hr (4.8 m3 per kw) of the aggregate 
input rating of all appliances installed in that 
space and an unconfined space as a space 
whose volume is not less than 50 cubic feet per 
1,000 BTU/hr (4.8 m3 per kw) of the aggregate 
input rating of all appliances installed in that 
space. Rooms connecting directly with the space 
in which the appliances are installed, through 
openings not furnished with doors, are 
considered a part of the unconfined space. 

This heater shall not be installed in a confined 
space or unusually tight construction unless 
provisions are provided for adequate combustion 
and ventilation air. Adjoining rooms are 
connecting only if there are odorless 
passageways or ventilation grills between them. 
 

Unusually Tight Construction 

 
The air that leaks around doors and windows 
may provide enough fresh air for combustion and   
ventilation. However, in buildings of unusually 
tight construction, you must provide additional 
fresh air. Unusually tight construction is defined 
as construction where: 
a) Walls and ceilings exposed to the outside 
atmosphere have a continuous water vapor 
retarder with a rating of one perm (6×10-11kg 
per pa-sec-m2) or less with openings gasket or 
sealed and   
 
b) Weather stripping has been added on 
openable windows and on doors and   
 
c) Caulking or sealants are applied to areas such 
as joints around window and door frames, 
between sole plates and floors, between wall 
ceiling joints, between wall panels, at 
penetrations for plumbing, electrical, and gas 
lines, and at other openings.   
 
If your home meets all of the three criteria above, 
you must provide additional fresh air. See 
“Ventilation Air from Outdoors”. If your home 
does not meet all of the three criteria above, 
proceed to “Determining Fresh-Air Flow for 
Heater Location”. 
   
 
 
 
 
 
 

 
 

Содержание GLDF18M-V

Страница 1: ...r some of our most popular products without requiring any adjustments Our product lines consist of vent free gas wall heaters a direct vent gas wall heater line kerosene and propane forced air heaters...

Страница 2: ...ater WARNING Keep the appliance area clear and free from combustible materials gasoline and other flammable vapors and liquids WARNING Due to high temperatures the appliance should be located out of t...

Страница 3: ...ings 13 The appliance must be isolated from the gas supply piping system by closing its equipment shut off valve during any pressure testing of the gas supply piping system at test pressures equal to...

Страница 4: ...d that has complied with all the requirement of the authority having jurisdiction PRODUCT FEATURES SAFETY PILOT This heater has a pilot with an Oxygen Depletion Sensing ODS safety shutoff system The O...

Страница 5: ...ate for heater location The Air Shutter is pre set for Liquid Propane use If using Natural Gas see Air Shutter section of manual Unit successfully tested o Installed by Company _______________________...

Страница 6: ...Compare parts with package contents list and diagram above If any part is missing or damaged do not attempt to assemble install or operate the product Contact customer service for replacement parts Be...

Страница 7: ...ater produces approximately one 1 ounce 30 ml of water for every 1 000 BTUs 0 3 KWs of gas input per hour Unvented room heaters are recommended as supplemental heat a room rather than a primary heat s...

Страница 8: ...f the aggregate input rating of all appliances installed in that space Rooms connecting directly with the space in which the appliances are installed through openings not furnished with doors are cons...

Страница 9: ...61 000 BTU Hr The space in the prior example is a confined space because the actual BTU hr used is more than the maximum BTU hr the space can support You must provide additional fresh air Your options...

Страница 10: ...quired size of ventilation grills or ducts Ventilation Air from Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two permanent openings one within 12 inches of th...

Страница 11: ...er creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next to vinyl or cloth wall coverings or operating heater where impurities such as tobacco smoke...

Страница 12: ...arance in Figure 7 are not met you must have a hood When using a hood there are still certain minimum clearances required Follow minimum clearances shown in Figure 7 when using a hood The gas log heat...

Страница 13: ...anent vent opening at all times Damper manufacture shall recommend means to accomplish this such as by a screw or bolt in the edge of the damper to prevent its closing or by a hole or holes in the dam...

Страница 14: ...eater So you will need to flip it over I recommend laying a cloth down so that the metal of the burner does not rub on the floor You will want to look for an oval shaped cover that has two screws You...

Страница 15: ...lide any further Once done you will tighten the screw on the cylinder then seal the air shutter cover again For more information please visit our website www thermablaster com You can contact us at 87...

Страница 16: ...burner holes as this can lead to sooting and an overall drop in the performance of your heater Logs should be placed sequentially from lowest to highest as the numbering indicates There are grooves on...

Страница 17: ...to top of chimney and the minimum height is 10 feet Chart shows minimum opening sq in for the given height and input rate FOR MASONRY BUILT FIREPLACES Free Opening Area Of Chimney Damper For Venting C...

Страница 18: ...upply This heater requires an external regulator not supplied Install the external regulator between the heater and gas supply CAUTION Avoid damage to regulator Hold gas regulator with wrench when con...

Страница 19: ...1 Disconnect heater with its appliance main gas valve control valve and equipment shutoff valve from gas supply piping system Pressures in excess of 1 2 PSIG will damage heater regulator 2 Cap off ope...

Страница 20: ...WHAT TO DO IF YOU SMELL GAS Open the window or door immediately Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supp...

Страница 21: ...the Control Knob counterclockwise from the Pilot setting to the desired number setting This should be done slowly in one motion without stopping between positions Knob will only turn if you have a st...

Страница 22: ...22 Figure 12 Control Panel Figure 13 Pilot System Figure 14 Pilot Blue Flame...

Страница 23: ...pressed air in a can You can use a vacuum cleaner in the blow position If using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could dama...

Страница 24: ...your gas supplier call the fire department IMPORTANT Operating heater where impurities in air exist may create odors Cleaning supplies paint paint remover cigarette smoke cements and glues new carpet...

Страница 25: ...when control knob is released Both control and igniter knobs are not fully pushed down Thermocouples are not heated enough External shutoff valve of gas supply is not fully opened Thermocouple connec...

Страница 26: ...leaners etc turn into white powder residue Turn heater off when using furniture polish wax carpet cleaner or similar products Heater produces unwanted odors Heater is burning vapors from paint hair sp...

Страница 27: ...27 ILLUSTRATED PARTS Model GLDF18M V...

Страница 28: ...nt 31 Frame assembly 10 Nozzle seat 32 LP ODS 11 LPG Nozzle 33 Chamber spacer 12 NG Nozzle 34 Battery pack 13 Air door washer 35 Bottom Strengthen strip No 2 14 Air door rod 36 Bottom Strengthen strip...

Страница 29: ...ce Performed Service Date Please register your product online at www thermablaster com or send in the registration form below to our office at Reecon North America 2515 Liberty Ave Pittsburgh PA 15222...

Отзывы: