Duct Sizing: 

For total duct lengths up to 25', use a

minimum 8" diameter round or equivalent rectangular. For longer 
lengths, use a minimum 10" diameter or equivalent. Grills or 
diffusers on the duct ends must not excessively restrict air flow.

Isolated Areas:

 Effective dehumidification may require that ducting 

be branched to isolated, stagnant areas. Use 6" or larger diameter 
branch ducting to each of two or three areas; use 4" or larger to 
each of four or more areas.

3.4C Ducting for Fresh Air

Fresh air can be brought into the structure by connecting a duct 
from outside to the 6" Ultra-Aire inlet and by turning on the fan 
switch or activating the humidity control on units with the humidity 
control panel. Activate the ventilation timer on units with the 
ventilating & humidity control panel to bring in fresh air. Advantages 
of this form of ventilation include:

1. Outside air is filtered before entering the building.
2.  Outside air will be dehumidified before entering if the Ultra-

Aire is running.

3.   Drawing air from outside and blowing inside aids in slightly 

pressurizing the structure. This helps prevent unfiltered and 
undehumidified air from entering elsewhere. It also reduces 
the potential for carcinogenic radon gas to enter and provides 
makeup air for open combustion and exhaust devices like the 
clothes drier, fireplace, and water heater.

4.  The need for an alternate ventilation device may be eliminated.

An insulated 6" diameter duct is generally sufficient to provide up 
to 125 CFM of outside air. Large quantities of outside air will impact 
Ultra-Aire performance positively or negatively, depending upon the 
difference between inside and outside air conditions. Consult the 
factory by calling 1-800-533-7533 for recommendations regarding 
the use of higher flows with your specific application. 

The outside air duct should be connected to the 6" round collar 
on top of the unit. The 6" round collar includes a manual damper. 
Adjust the manual damper to provide the desired amount of fresh air 
for ventilation. The amount of fresh air should be based on the size 
and occupancy of the residence. If you are unsure of your ventilation 
air requirements, consult the factory by calling 1-800-533-7533 for 
assistance. 

3.4D Installation in a Basement or Crawlspace with an 

Existing Forced Air HVAC System.

If the structure in which the Ultra-Aire is to be installed has an 
existing forced air HVAC system, utilize the HVAC system to make 
the Ultra-Aire installation easier. 

If the existing system has multiple returns, select one to disconnect 
from the existing forced air system and use it for the dedicated 
Ultra-Aire return. Always select a return from a central location 
in the structure in an area that is always open to the rest of the 

structure. Do not use a return from a room that may have its door 
closed much of the time.

Basement Installation: 

Locate a separate return for the Ultra-Aire 

in a central area of the structure. Duct the supply of the Ultra-Aire 
to a 8" x 8" x 8" tee/damper that is 30% open to the basement. 
Duct the other side of the tee to the air return of the existing HVAC 
system. If the existing HVAC system has a central return, duct the 
other side of the tee to the air supply of the existing HVAC system. 
Connect a duct from outside to the 6" collar of the Ultra-Aire if you 
wish to provide fresh make-up air.

Crawlspace Installation: 

Locate a separate return for the Ultra-

Aire in a central area of the structure. Duct the supply of the 
Ultra-Aire to a 8" x 8" x 8" tee/damper that is 30% open to the 

FOR HVAC INSTALLER ONLY

4

5

Ultra-Aire 100V Installer’s & Owner’s Manual

Ultra-Aire 100V Installer’s & Owner’s Manual

Содержание Ultra-Aire DEH 3000

Страница 1: ...fresh outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can...

Страница 2: ...your Ultra Aire indoor air quality system Read and save these instructions The device is designed to be installed INDOORS IN A SPACE THAT IS PROTECTED FROM RAIN AND FLOODING Install the unit with spa...

Страница 3: ...building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short piece cut from the end o...

Страница 4: ...calling 1 800 533 7533 for recommendations regarding the use of higher flows with your specific application The outside air duct should be connected to the 6 round collar on top of the unit The 6 roun...

Страница 5: ...ake sure none of the compressor tubes are pressed against the cabinet or front panel A length of 10 feet or more of acoustical flex ducting on the outlet of the Ultra Aire will reduce air noise from t...

Страница 6: ...r of the timer face The reset button is the small recessed button with an R beneath it located below the 1 7 and h buttons Press the reset button in until the display disappears Release the reset butt...

Страница 7: ...pot Test Method 52 76 This filter is much more efficient than the standard air filter and is able to catch much smaller particles that can aggravate allergies The high efficiency air filter is 4 inche...

Страница 8: ...the unit to contact the red lead or the white lead from the unit or damage to the transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation contro...

Страница 9: ...Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n...

Страница 10: ...n handling the high efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 7 Service CAUTION Se...

Страница 11: ...or the correct charge weight and refrigerant type 7 5 Fan Replacement The centrifugal fan has a PSC motor and internal thermal overload protection If defective the complete assembly must be replaced 1...

Страница 12: ...t carbon deposits the burn out occurred while the compressor was not rotating Contaminants are therefore largely confined to the compressor housing A single installation of liquid and suction line fil...

Страница 13: ...gerant suction tube between the accumulator and the compressor It will automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the evapo...

Страница 14: ...ULTRA AIR 100V ELECTRICAL SCHEMATIC 14 Ultra Aire 100V Installer s Owner s Manual...

Страница 15: ...ULTRA AIRE 100V PICTORIAL ELECTRICAL DIAGRAM 15 Ultra Aire 100V Installer s Owner s Manual...

Страница 16: ...anasonic 2R12S3R126A 6A 10 4022144 1 Compressor Overload TI MRA98706 673 not shown 11 4021396 1 Condenser Coil 12 4022445 1 Cord Wire Harness 13 4025087 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 I...

Страница 17: ...32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Timer Humidity not shown 36 4025560...

Страница 18: ...ULTRA AIRE 100V EXTERNAL INSULATION KIT 18 Ultra Aire 100V Installer s Owner s Manual...

Страница 19: ...rough the rubber grommet 4 Place the box in the hole and put the mounting tabs through the slots in the box sides as shown 5 Place the two 3 4 long 8 screws through the tab slots and into the holes in...

Страница 20: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsib...

Страница 21: ...rmastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purp...

Отзывы: