Ultra-Aire does not run, try turning the humidity control clockwise 
until it reaches the stop and the knob pointer points at “ON”.

The Ultra-Aire is equipped with a automatic defrost mechanism. 
If the Ultra-Aire operates in conditions that develop frost on the 
evaporator, it will sense the frost build-up and automatically defrost 
the evaporator. The Ultra-Aire may not appear to be operating 
correctly during the defrost sequence, but once the defrost is 
completed, the Ultra-Aire will resume dehumidifying.

7.7B Programmable Ventilation Timer

The ventilation timer controls the fan and the motorized fresh 
air damper. When the ventilation timer is activated, the central 
conditioning unit will circulate the indoor air, and bring in fresh air 
from outside. The ventilation timer should be set for the required 
ventilation of the residence. The home should be ventilated with 
fresh air whenever it is occupied. If the Ultra-Aire fails to ventilate 
as expected, check that the time on the timer is correct. For the 
timer to carry out the program schedule, the slide switch in the 
upper left corner on the timer must be set to “AUTO”. The slide 
switch in the upper right corner of the Ultra-Aire must be set to 
“RUN”. Also check the programs on the timer to be sure that the 
timer is calling for ventilation at the correct times. If the timer fails 
to operate or operates erratically, reset the timer; see section 3.5 of 
this manual.

7.8 Defrost Thermostat

The defrost thermostat is attached to the refrigerant suction tube 
between the accumulator and the compressor. It will automatically 
shut the compressor off if the low side refrigerant temperature 
drops due to excessive frost formation on the evaporator coil. 
The fan will continue to run, causing air to flow through the 
evaporator coil and melt the ice. When the ice has melted, the 
evaporator temperature will rise and the thermostat will restart the 
compressor.

7.9 Electric Ventilation Damper

The electric ventilation damper is controlled by the ventilation timer. 
The damper will open when the ventilation timer is activated to allow 
fresh air into the structure through the 6" diameter fresh air inlet duct. 
The electric ventilation damper will remain closed when the ventilation 
timer is not activated to prevent over-ventilating the structure when 
the unit is dehumidifying or recirculating the indoor air.

The electric ventilation timer operates on 24 Vac from the control 
circuit. DO NOT connect high voltage to the damper motor or 
damage to the motor may result. DO NOT force the blade of the 
damper by hand or damage to the damper motor may result.

The damper opens in one direction only. The damper rotates very 
slowly, allow sufficient time for the damper to cycle. The damper 
will take approximately 1 minute to cycle from closed to open or 
from open to closed.

If the electric ventilation damper fails to operate:

1.  Check that the wiring is correct and that voltage is present at 

the damper motor.

2.  Check for any obstruction inside the damper.

If the electric ventilation damper fails to operate after performing 
these checks, it must be replaced.

FOR HVAC INSTALLER AND HOMEOWNER

13

Ultra-Aire 100V Installer’s & Owner’s Manual

Содержание Ultra-Aire DEH 3000

Страница 1: ...fresh outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can...

Страница 2: ...your Ultra Aire indoor air quality system Read and save these instructions The device is designed to be installed INDOORS IN A SPACE THAT IS PROTECTED FROM RAIN AND FLOODING Install the unit with spa...

Страница 3: ...building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short piece cut from the end o...

Страница 4: ...calling 1 800 533 7533 for recommendations regarding the use of higher flows with your specific application The outside air duct should be connected to the 6 round collar on top of the unit The 6 roun...

Страница 5: ...ake sure none of the compressor tubes are pressed against the cabinet or front panel A length of 10 feet or more of acoustical flex ducting on the outlet of the Ultra Aire will reduce air noise from t...

Страница 6: ...r of the timer face The reset button is the small recessed button with an R beneath it located below the 1 7 and h buttons Press the reset button in until the display disappears Release the reset butt...

Страница 7: ...pot Test Method 52 76 This filter is much more efficient than the standard air filter and is able to catch much smaller particles that can aggravate allergies The high efficiency air filter is 4 inche...

Страница 8: ...the unit to contact the red lead or the white lead from the unit or damage to the transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation contro...

Страница 9: ...Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n...

Страница 10: ...n handling the high efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 7 Service CAUTION Se...

Страница 11: ...or the correct charge weight and refrigerant type 7 5 Fan Replacement The centrifugal fan has a PSC motor and internal thermal overload protection If defective the complete assembly must be replaced 1...

Страница 12: ...t carbon deposits the burn out occurred while the compressor was not rotating Contaminants are therefore largely confined to the compressor housing A single installation of liquid and suction line fil...

Страница 13: ...gerant suction tube between the accumulator and the compressor It will automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the evapo...

Страница 14: ...ULTRA AIR 100V ELECTRICAL SCHEMATIC 14 Ultra Aire 100V Installer s Owner s Manual...

Страница 15: ...ULTRA AIRE 100V PICTORIAL ELECTRICAL DIAGRAM 15 Ultra Aire 100V Installer s Owner s Manual...

Страница 16: ...anasonic 2R12S3R126A 6A 10 4022144 1 Compressor Overload TI MRA98706 673 not shown 11 4021396 1 Condenser Coil 12 4022445 1 Cord Wire Harness 13 4025087 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 I...

Страница 17: ...32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Timer Humidity not shown 36 4025560...

Страница 18: ...ULTRA AIRE 100V EXTERNAL INSULATION KIT 18 Ultra Aire 100V Installer s Owner s Manual...

Страница 19: ...rough the rubber grommet 4 Place the box in the hole and put the mounting tabs through the slots in the box sides as shown 5 Place the two 3 4 long 8 screws through the tab slots and into the holes in...

Страница 20: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsib...

Страница 21: ...rmastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purp...

Отзывы: