6.    Compressor terminal C and overload terminal 1: 

No continuity indicates a defective overload lead.

7.    Overload terminals 1 and 3: 

If there is no continuity, the overload may be tripped. Wait 
10 minutes and try again. If there is still no continuity, it is 
defective and must be replaced.

8.    Compressor terminal C and compressor case: Continuity 

indicates a grounded motor. The compressor must be 
replaced.

9.    Disconnect the wires from the run capacitor. Set the 

ohmmeter to the Rx1 scale. The capacitor is shorted and 
must be replaced if continuity exists across its terminals. 
If there is no needle movement with the meter set on 
the Rx100000 scale, the capacitor is open and must be 
replaced.

10.   Reconnect the wires to the compressor and capacitor. Plug 

in and turn on the unit. If the compressor fails to start, 
replace the run capacitor.

11.  If the unit still does not start, adding a hard-start kit (relay & 

capacitor) will provide greater starting torque. If this doesn't 
work, the compressor has an internal mechanical defect and 
must be replaced.

7.6B Replacing a Burned Out Compressor

The refrigerant and oil mixture in a compressor is chemically 
very stable under normal operating conditions. However, when an 
electrical short occurs in the compressor motor, the resulting high 
temperature arc causes a portion of the refrigerant oil mixture to 
break down into carbonaceous sludge, a very corrosive acid, and 
water. These contaminants must be carefully removed otherwise 
even small residues will attack replacement compressor motors and 
cause failures.

The following procedure is effective only if the system is monitored after 
replacing the compressor to insure that the clean up was complete.

1.    This procedure assumes that the previously listed compressor 

motor circuit tests revealed a shorted or open winding. If so, 
cautiously smell the refrigerant from the compressor service 
port for the acid odor of a burn out. WARNING: The gas could 
be toxic and highly acidic. If no acid odor is present, skip down 
to the section on changing a non-burn out compressor.

2.    Remove and properly dispose of the system charge. DO NOT 

vent the refrigerant indoors or allow it to contact your eyes 
or skin.

3.    Remove the burned out compressor. Use rubber gloves if there 

is any possibility of contacting the oil or sludge.

4.    To facilitate subsequent steps, determine the type of burn 

out that occurred. If the discharge line shows no evidence 
of sludge and the suction line is also clean or perhaps has 
some light carbon deposits, the burn out occurred while the 

compressor was not rotating. Contaminants are therefore 
largely confined to the compressor housing. A single 
installation of liquid and suction line filter/driers will probably 
clean up the system. If sludge is evident in the discharge line, 
it will likely be found in the suction line. This indicates the 
compressor burned out will running. Sludge and acid have 
been pumped throughout the system. Several changes of the 
liquid and suction filter/driers will probably be necessary to 
cleanse the system.

5.    Correct the system fault that caused the burn out. Consult the 

factory for advice.

6.    Install the replacement compressor with a new capacitor and 

an oversized liquid line filter. In a running burn out, install an 
oversized suction line filter/drier between the accumulator and 
compressor. Thoroughly flush the accumulator with refrigerant 
to remove all trapped sludge and to prevent the oil hole from 
becoming plugged. A standing burn out does not require a 
suction line filter/drier.

7.    Evacuate the system with a good vacuum pump and 

accurate vacuum gauge. Leave the pump on the system for 
at least an hour. 

8.    Operate the system for a short period of time, monitoring the 

suction pressure to determine that the suction filter is not 
becoming plugged. Replace the suction filter/drier if pressure 
drop occurs. If a severe running burn out has occurred, several 
filter/driers may have to be replaced to remove all of the acid 
and moisture. 

NOTE: NEVER use the compressor to evacuate 

the system or any part of it.

7.6C Replacing a Compressor, Nonburn Out

Remove the refrigerant from the system. Replace the compressor 
and liquid line filter/drier. Charge the system to 50 PSIG and check 
for leaks. Remove the charge and weigh in the refrigerant quantity 
listed on the nameplate. Operate the system to verify performance.

7.7 Remote Controls

The Ultra-Aire is controlled by devices mounted on a panel that is 
remote from the unit. You may or may not have the devices listed 
below depending on the model of the remote control panel that 
you purchased. If the Ultra-Aire fails to operate as desired, always 
check the settings of the controls to insure that they are correct. 
Check that the controls are receiving 24Vac from the Ultra-Aire. 
Check the connections between the Ultra-Aire, the control panel, 
and the field control wiring.

7.7A Humidity Control

The humidity control is an adjustable switch that closes when the 
relative humidity of the air in which it is located rises to the dial set 
point. It opens when the RH drops 4 to 6% below the set point. If the 

FOR HVAC INSTALLER AND HOMEOWNER

12

Ultra-Aire 100V Installer’s & Owner’s Manual

Содержание Ultra-Aire DEH 3000

Страница 1: ...fresh outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can...

Страница 2: ...your Ultra Aire indoor air quality system Read and save these instructions The device is designed to be installed INDOORS IN A SPACE THAT IS PROTECTED FROM RAIN AND FLOODING Install the unit with spa...

Страница 3: ...building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short piece cut from the end o...

Страница 4: ...calling 1 800 533 7533 for recommendations regarding the use of higher flows with your specific application The outside air duct should be connected to the 6 round collar on top of the unit The 6 roun...

Страница 5: ...ake sure none of the compressor tubes are pressed against the cabinet or front panel A length of 10 feet or more of acoustical flex ducting on the outlet of the Ultra Aire will reduce air noise from t...

Страница 6: ...r of the timer face The reset button is the small recessed button with an R beneath it located below the 1 7 and h buttons Press the reset button in until the display disappears Release the reset butt...

Страница 7: ...pot Test Method 52 76 This filter is much more efficient than the standard air filter and is able to catch much smaller particles that can aggravate allergies The high efficiency air filter is 4 inche...

Страница 8: ...the unit to contact the red lead or the white lead from the unit or damage to the transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation contro...

Страница 9: ...Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n...

Страница 10: ...n handling the high efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 7 Service CAUTION Se...

Страница 11: ...or the correct charge weight and refrigerant type 7 5 Fan Replacement The centrifugal fan has a PSC motor and internal thermal overload protection If defective the complete assembly must be replaced 1...

Страница 12: ...t carbon deposits the burn out occurred while the compressor was not rotating Contaminants are therefore largely confined to the compressor housing A single installation of liquid and suction line fil...

Страница 13: ...gerant suction tube between the accumulator and the compressor It will automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the evapo...

Страница 14: ...ULTRA AIR 100V ELECTRICAL SCHEMATIC 14 Ultra Aire 100V Installer s Owner s Manual...

Страница 15: ...ULTRA AIRE 100V PICTORIAL ELECTRICAL DIAGRAM 15 Ultra Aire 100V Installer s Owner s Manual...

Страница 16: ...anasonic 2R12S3R126A 6A 10 4022144 1 Compressor Overload TI MRA98706 673 not shown 11 4021396 1 Condenser Coil 12 4022445 1 Cord Wire Harness 13 4025087 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 I...

Страница 17: ...32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Timer Humidity not shown 36 4025560...

Страница 18: ...ULTRA AIRE 100V EXTERNAL INSULATION KIT 18 Ultra Aire 100V Installer s Owner s Manual...

Страница 19: ...rough the rubber grommet 4 Place the box in the hole and put the mounting tabs through the slots in the box sides as shown 5 Place the two 3 4 long 8 screws through the tab slots and into the holes in...

Страница 20: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsib...

Страница 21: ...rmastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purp...

Отзывы: