Turn off the 7-day timer by moving all the spades out. Turn 
off all the remote timers and the dehumidistat (if used). If the 
circuit breaker trips, locate a short in the wiring. If the circuit 
breaker does not trip, activate the 7-day timer. If the circuit 
breaker then trips, check the blower motor.

5.2 Blower Operates on One Speed Only

Operates On Low Speed Only:

If the blower operates only on low speed, deactivate the 
7-day timer so that unit is not running. Activate one of the 
optional controls and then check for voltage to the relay coil 
(terminals 7 and 8). See Figure 3. If voltage is not present, 
check for a loose wire or a defective optional control. If 
voltage is present, check for voltage between relay terminal 
4 and ground. If there is no voltage, the relay is defective. If 
there is voltage at terminal 4 and the motor does not operate, 
the high speed winding of the blower motor is defective. 
Replace the blower.

Operates On High Speed Only:

High speed operation of the blower has priority over low 
speed. Verify that all the optional controls are in the off 
position. If the blower operates on high speed constantly, 
check for voltage between relay terminals 7 and 8. If voltage 
is present, one of the optional controls is not opening and is 
defective.

If the blower operates only on high speed (when the optional 
controls are activated) and is off the rest of the time, check 
that the segments on the 7-day timer are moved to the 
center of the dial, thus calling for low speed ventilation. If the 
blower does not run with the segments in and the optional 
controls off, check for voltage between timer terminal 5 
and ground. If terminal 5 does not have voltage, the timer is 
defective. If terminal 5 has voltage and relay terminal 5 does 
not have voltage, the relay is defective. If relay terminal 5 
has voltage, the low speed winding of the blower motor is 
defective.

5.3 7-Day Timer Does Not Advance

Check for voltage between timer terminals 1 and 2. If voltage 
is present and the timer does not advance, the timer motor is 
defective and the timer must be replaced.

5.4 Fan Motor

If the blower motor fails to operate when voltage is present 
at its leads, the motor is defective and the blower must be 
replaced.

5.5 Warranty

The Ultra-Aire Quiet Vent is guaranteed for two years from 
the date of installation against all manufacturing defects 
provided the Ultra-Aire Quiet Vent has been installed, 
operated, and maintained as stated in this manual. This 
warranty is limited to the repair or replacement of the 
equipment, F.O.B. MADISON, WI. Call the factory at 1-800-
533-7533.

6. Service Parts

Item  Part Number  Qty.  Description

1  

4026929 

1  

Blower, w/Capacitor, 115V 

2  

4019782  

4  

Mounting Strap, Rubber

3  

4019649  

1  

Relay, DPDT, 120V, 10A

4  

4019648  

1  

Timer, 7-Day  

 

 

 

(Diehl TA-4073, Model 880)

5  

4019641  

1  

Wire Harness, L1

6  

4019642  

1  

Wire Harness, L2

7  

4019643  

1  

Wire Harness, Blue

8  

4019644  

1  

Wire Assembly, Red

9  

4019645  

1  

Wire Assembly, Green

10  

4019654  

1  

Wiring Diagram

FOR HVAC INSTALLER ONLY

Содержание Quiet-Vent Ventilation System

Страница 1: ...680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales thermastor com TS 174B INSTALLER S OWNER S MANUAL HVAC INSTALLER PLEASE LEAVE MANUAL FOR HOMEOWNER P N 4019663 Serial No ________________________ Install Date ___________ Sold by ...

Страница 2: ... reduce the risk of fire electric shock or injury to persons observe the following A Installation work and electrical wiring must be done by qualified person s in accordance with all applicable codes and standards including fire rated construction B Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent backdrafting Foll...

Страница 3: ... from the Ultra Aire Quiet Vent see paragraph F In cold climates the unit should be located in a heated space to prevent condensation from forming inside the cabinet A basement or utility room is an ideal location If the Ultra Aire Quiet Vent and its ducting must be located in a unheated space in a cold climate they must be insulated to prevent condensation from forming in the system If the Ultra ...

Страница 4: ... stale air connect a six inch insulated flexible duct from the outlet of the Ultra Aire Quiet Vent to a dampered six inch wall cap If the length of the exhaust duct exceeds 50 ft an 8 duct should be used All the ducts must be insulated when they are located in non heated space in a cold climate Flexible duct can be spliced by threading the ends of the ducts into each other 3 turns To reduce leakag...

Страница 5: ...ired to control moisture and odors additional spades can be moved in If the home becomes too dry decrease the hours of low speed operation 3 2 Using Remote Timers Estimate the ventilation time required and set it on the timer Activate the timer whenever moisture or odors are generated in the room If timers are not available locally they may be ordered with the Ultra Aire Quiet Vent 3 2 Adjusting t...

Страница 6: ...the segments on the 7 day timer are moved to the center of the dial thus calling for low speed ventilation If the blower does not run with the segments in and the optional controls off check for voltage between timer terminal 5 and ground If terminal 5 does not have voltage the timer is defective If terminal 5 has voltage and relay terminal 5 does not have voltage the relay is defective If relay t...

Страница 7: ...y the period of time if any that the Ultra Aire Quiet Vent is out of service while awaiting covered warranty service UPON THE EXPIRATION OF THE WRITTEN WARRANTY APPLICABLE TO THE Ultra Aire Quiet Vent VENTILATING SYSTEM OR ANY PART THEREOF ALL OTHER WARRANTIES IMPLIED BY LAW INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE SHALL ALSO EXPIRE ALL WARRANTIES MADE BY THERMA STOR LLC ARE ...

Страница 8: ...any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phone 608 222 5301 Fax 608 222 1447 Web www thermastor com Email sales thermastor com Ultra Aire Quiet Vent Installer s Owner s Manual ...

Отзывы: