5.2D Dehumidifier lockout/activation:
AC sensor feature
The control has the ability to activate the dehumidifier or
deactivate the dehumidifier when the air conditioner is running.
Standard wire colors for thermostats are as follows:
Description
Color
Terminal code
24VAC Return
Red
R
Call for Heat
White
W or W1
Force Fan On
Green
G
Compressor
Call for Cooling Yellow
Y or Y1
DEHUMIDIFIER DEACTIVATES WHEN THE
AIR-CONDITIONER IS RUNNING
• The common wire on the thermostat transformer
(black) needs to be wired with the yellow wire
from the dehumidifier.
• The Yellow wire from the thermostat must be
wired to the AC off sensor terminal.
DEHUMIDIFIER ACTIVATES WHEN THE
AIR-CONDITIONER IS RUNNING
• The common wire on the thermostat transformer
(black) needs to be wired with the yellow wire
from the dehumidifier.
• The Yellow wire from the thermostat must be
wired to the AC on sensor terminal.
5.2E Location
Install the remote control panel in a central area of
the structure where it will sense the relative humidity
of the structure accurately. Do not install the control
panel where it may not accurately sense the relative
humidity such as near HVAC supply registers, near exterior doors and windows, or near a pool or spa.
5.2F Testing
After wiring connections have been made, verify connections. First, make sure the white wire from the
base unit is not wired directly to the DEH 3000 control. There must be a motorized damper in series
with these connections, or the white wire must not be connected to the control. Mis-wiring may result in
transformer damage.
FOR HVAC INSTALLER AND HOMEOWNER
FOR INSTALLER AND HOMEOWNER
FOR HVAC INSTALLER AND OWNER