the compressor. The compressor evacuates the cool 
refrigerant gas from the accumulator and compresses it to 
a high pressure and temperature to repeat the process.

4.2 Troubleshooting

No dehumidification, neither hour meter display nor 
compressor run and POWER button does not turn ON.

1.   Unit unplugged or no power to outlet
2.   Defective control board
3.   Loose connection in internal wiring

No dehumidification, neither hour meter display nor 
compressor run with POWER button ON.

1.   Defective control board
2.   Loose connection in internal wiring

Some dehumidification, air mover runs continuously but 
compressor only runs sporadically.

1.   Unit is in defrost cycle, DEFROST light on
2.   Defrost thermistor defective or loose
3.   Loose connection in compressor circuit
4.   Defective compressor overload
5.   Defective compressor
6.   Defective relay
7.   Low refrigerant charge
8.  Defrost thermistor detached from coil

No dehumidification, air mover runs but compressor does 
not.

1.   Bad connection in compressor circuit
2.   Safety float switch closed, check pump reservoir
3.   Defective compressor capacitor
4.   Defective compressor overload
5.   Defective compressor
6.   Defective control board
7.  Low refrigerant charge

Air mover does not run. Compressor runs briefly but cycles 
on and off.

1.   Loose connection in blower circuit
2.   Obstruction prevents impeller rotation
3.   Defective air mover
4.  Defective control board.

Unit removes some water but not as much as expected.

1.   Air temperature and/or humidity have dropped
2.   Humidity meter and/or thermometer used are out of 

calibration

3.   Unit has entered defrost cycle
4.   Air filter dirty

5.   Defective defrost thermistor
6.   Low refrigerant charge
7.   Air leak such as loose front cover
8.   Defective compressor
9.   Restrictive exhaust or inlet ducting
10. Defrost thermistor detached from coil

Unit runs but does not pump water.

1.   Hose kinked or plugged
2.   Pump motor defective
3.   Pump check valve plugged
4.   Bad connection in pump circuit
5.   Hose disconnected internally
6.   Defective control board

Unit pumps water automatically but not when PURGE 
button is pushed.

1. Bad connection in PURGE button circuit
2. Defective control board

Evaporator coil frosted continuously, low dehumidifying 
capacity.

1. Defrost thermistor loose or defective
2. Low refrigerant charge

Compressor runs with POWER button OFF.

1. Defective relay
2. Defective control board
3. Upper housing not sealed to tower

No hour meter display when the HOURS button is pressed.

1.   Battery charge is low. Replace battery
2.   Defective control board

Bypass door remains open.

1.   Ambient temperature above set point.
2.  Defective actuator.
3.  Defective board.
4.  Loose connection between board and actuator.

Bypass door remains closed.

1.  Ambient temperature below set point.
2.  Defective actuator.
3.  Defective board.
4.  Loose connection between board and actuator.
5.  Loose temperature sensor connection.

Содержание Phoenix 270HTx

Страница 1: ...12 intake 10 exhaust Solid State Controls Easy to read and operate Recessed 12 Wheels Allows greater maneuverability on the job site and efficient storage Rolls over obstacles with ease MERV 11 Pleat...

Страница 2: ...walls and other obstructions to air flow Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 2 1 Transporting the Phoenix 270HTx 2 2 2 Location 2 2 3 Electrical Requirements 3 2 4 Conden...

Страница 3: ...oir before transport or storage Turn off the power and allow the plugged in dehumidifier to rest 15 minutes before the final purge 2 8 Hour Meter The digital hour meter displays the cumulative and job...

Страница 4: ...d If the unit will not be exposed to freezing temperatures an alternative to reduce biological growth is to flush the unit with a bio fungicide that is approved for use with copper aluminum and polyet...

Страница 5: ...cuit 2 Obstruction prevents impeller rotation 3 Defective air mover 4 Defective control board Unit removes some water but not as much as expected 1 Air temperature and or humidity have dropped 2 Humid...

Страница 6: ...ng the pump bracket to the base 5 Replace the pump hose wiring bolts and cover in the reverse order 4 6 Refrigerant Charging If the refrigerant charge is lost due to service or a leak a new charge mus...

Страница 7: ...7 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 5 Wiring Diagram 4028595...

Страница 8: ...peller 15mfd 371V 1 4025224 14 Thermistor Coil 1 4027278 15 Thermistor Bulkhead 1 4028581 16 Battery AA 4 8523901 17 Cord 115V 25 1 4025078 18 Compressor 10 2KBTU R410a 1 4029176 19 Overload Compresso...

Страница 9: ...9 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 This page intentionally left blank...

Страница 10: ...anty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts o...

Отзывы: