5.2 Inlet Duct Kit (P/N 4028610)

A factory designed inlet duct kit can be purchased to accept 
12" ducting. Contact your dealer or call 1-800-533-7533 to 
order.

6. Operation

6.1 Humidity Control Adjustment

The humidity control is an adjustable switch that closes when 

the relative humidity of the air in which it is located rises to 

the dial set point. It opens when the RH drops 4 to 6% below 

the set point.

Approximate Humidity Levels Per Setting

“Dry”  

20% to 30% Relative Humidity

“Normal”   50% Relative Humidity (Recommended)
“Humid”  80% to 90% Relative Humidity

The dehumidifier will run until the relative humidity (RH) is 

reduced to the humidity control dial setting. 
Quality humidity meters are available from the factory and 

are recommended to accurately monitor humidity levels. 

Refer to the options and accessories table in this document.

6.2 Blower (Fan) Switch

Turning the blower switch to 

“FAN ON” 

will cause the unit’s 

internal blower to run continuously, whether the unit is 

dehumidifying or not. This function is desirable if the unit is 

used for air circulation.

Turning the blower switch to 

“FAN AUTO”

 will cause 

the unit’s internal blower to run only while the unit is 
dehumidifying.

7. Maintenance

 WARNING!

 

NOTE: Do not operate the unit 

without the filter or with a less effective filter. The 

heat exchange coils inside the unit could become 

clogged and require disassembly to clean.

7.1 Air Filter

The Santa Fe Max Dry Dual XT ships with a standard MERV 
6 efficient pleated fabric filter. This should be checked 
every six months. The pleated fabric filter can generally be 
vacuumed clean several times before needing replacement. 
Operating the unit with a dirty filter will reduce dehumidifier 
capacity and efficiency and may cause the compressor to 
cycle on and off unnecessarily. Replacement filters can be 
ordered from your dealer or by calling 1-800-533-5333.

8. Service

 WARNING! 

Servicing the Santa Fe Max 

Dry Dual XT with its high pressure refrigerant 
system and high voltage circuitry presents a 
health hazard which could result in death, serious 
bodily injury, and/or property damage. Only 

qualified service people should service this unit.

8.1 Technical Description

The Santa Fe Max Dry Dual XT uses a refrigeration system 
similar to an air conditioner’s to remove heat and moisture 
from incoming air, and add heat to the air that is 
discharged. Hot, high pressure refrigerant gas is routed from 
the compressor to the condenser coil. The refrigerant is 
cooled and condensed by giving up its heat to the air that is 
about to be discharged from the unit. The refrigerant liquid 
then passes through a filter/drier and capillary tubing which 
cause the refrigerant pressure and temperature to drop. It 
next enters the evaporator coil where it absorbs heat from 
the incoming air and evaporates.

Santa Fe Max Dry Dual XT refrigeration system

The evaporator operates in a flooded condition, which 
means that all the evaporator tubes contain liquid 

Santa Fe Max Dry Dual XT OWNER’S AND INSTALLER’S MANUAL

5

Santa Fe Max Dry Dual XT Installer’s & Owner’s Manual

Содержание 4027450

Страница 1: ...r com Free standing Moisture Control for Large Areas n High capacity n High efficiency n Environmentally friendly n Patent pending dual air distribution INSTALLER S OWNER S MANUAL HVAC INSTALLER PLEAS...

Страница 2: ...ot sit or stand on the unit or use as a shelf or table Before leaving the unit unattended ensure children do not have access to the equipment Do not allow children to play with or near the unit or in...

Страница 3: ...e exhaust of the unit within 1 of a wall or obstruction Do not place the unit near open water 4 1A No Ducting fig 1 The simplest installation is to place the Santa Fe Max Dry Dual XT with no ducting T...

Страница 4: ...50 RH Use of a ground fault circuit interrupter GFCI protected circuit is recommended The unit should not be used in areas prone to flooding CAUTION For proper drainage the unit must be mounted so th...

Страница 5: ...s with a standard MERV 6 efficient pleated fabric filter This should be checked every six months The pleated fabric filter can generally be vacuumed clean several times before needing replacement Oper...

Страница 6: ...n capacitor n Blower runs with fan switch AUTO but compressor cycles on off 1 Low ambient temperature and or humidity causing unit to cycle through defrost mode 2 Defrost thermostat defective 3 Defect...

Страница 7: ...7533 11 Santa Fe Max Dry Dual XT Optional Remote Humidity Control CAUTION This should only be performed by a qualified electrician A 120Vac remote humidity control is available from the factory This...

Страница 8: ...er any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Res...

Страница 9: ...uced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved PO Box 8680...