Therma Q AGDIR 0120 Скачать руководство пользователя страница 9

ISSUE 2016 Rev 1 - Installation Manual 

ThermaQ 

 

Insulation of the Temperature and Pressure Relief Valve 
 
Components for insulating the TPRV are supplied in order to retain heat and energy. Installation instructions are provided with the insulation 
cover. 
 
Discharge Pipework and Tundish 
 
Note: This information is not exhaustive, and if in doubt, seek advice. Full details of Building Regulation G3, is available from: 
www.planningportal.gov.uk 
 
The discharge from both the temperature relief and expansion relief valves can be joined together via a 15mm end feed tee. Water should only 
be discharged when there is a fault with the system. 
 
The discharge water must not collect in this pipe-work and flow freely to the tundish. This tundish should be vertically mounted in a visible 
location in the same space as the hot water storage system, fitted as close as possible with 600mm of the safety device e.g. the temperature 
relief valve. The discharge pipework from this tundish must be routed in accordance with part G3 of the Building Regulations.  
 
This discharge should be visible at the tundish. For people with impaired vision or mobility, consider installing a safety device to alert them to 
when discharge takes place. For more information in this situation see the building regulations. 
 
a)

 

The discharge pipe (D2) from the Tundish should have a vertical section of pipe 300mm long below the Tundish before any elbows    
or bends in the pipework.  

b)

 

This pipe should then be installed with a continuous fall of at least 1 in 200 thereafter. 

c)

 

The pipe must be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic 
resistance exceeds that of a straight pipe 9m long i.e. discharge pipes between 9m and 18m equivalent resistance length should be at 
least two sizes larger than the nominal outlet size of the safety device, between 18 and 27m at least 3 times larger and so on. Bends 
must be taken into account in calculating the flow resistance. An alternative approach for sizing discharge pipes would be to follow 
BS6700 Specification for the design installation, testing and maintenance of services supplying water for domestic use within 
buildings and their curtilages. 

 
From the tundish, pipework should terminate in a safe place where there is no danger to persons in the vicinity of the discharge. Examples of 
acceptable discharge arrangements include: 
 
1.

 

To a trapped gully with the outlet below a fixed grating and above water seal. 

2.

 

Downward discharges to low level, within 100mm, above external surfaces such as a car park, hard standing, grassed area with a 
protective wire cage to prevent contact but retaining visibility of discharge. 

3.

 

Discharge at high level into a metal hopper and metal downpipe with the termination point clearly visible or onto a roof capable of 
withstanding high temperature discharge and at least 3m away from plastic guttering system. 

 
Building Regulation G3 allows for the usage of non-metallic pipework within the tundish discharge (D2): The discharge pipe (D2) should be 
made of a) metal or b) other material that has demonstrated to be capable of safely withstanding high temperatures of water discharges and is 
clearly and permanently marked to identify the product and the performance standard. The discharge should not be connected to a soil 
discharge stack unless it can be demonstrated of safely withstanding the high temperature of water discharge, in which case it should; 
1.

 

Contain a mechanical seal, not a water trap, which allows water into the branch pipe but not foul air from the drain to be ventilated 
through the tundish. 

2.

 

Be a separate branch pipe with no sanitary appliances connected to it. 

3.

 

Plastic pipes used as branch pipes with the discharge should be Polybutylene (PB) or cross linked polythene (PEX) complying with 
national standards such as Class S of B7291-2:2006 or Class S of BS7291-3:2006 respectively. 

4.

 

Be continuously marked with a warning that no sanitary appliances should be connected to the pipe. 

5.

 

Plastic pipes should be joined and assembled with fittings appropriate to the circumstances in which they are used as set out in BS 
EN 1043-1:2002 

 

The foregoing is an appraisal of Building Regulation detail and it is essential the installer gains knowledge of the full requirements 
prior to product installation.

 

 
Schematic  
 
 
 
 
 
 
 
 

Содержание AGDIR 0120

Страница 1: ...INSTALLATION MANUAL Issue 2016 Rev 1 Tested to BS EN 12897 2006 FOR MORE INFORMATION GO TO WWW THERMAQ CO UK Note By installing this product you agree to be bound by our Conditions of Sale found with...

Страница 2: ...roduct Specifications 3 General Installation and Commissioning 6 Service and Maintenance 9 Fault Finding 10 Benchmark Commissioning Checklist 15 Service Record 16 User Guide and Customer Service 17 Wi...

Страница 3: ...ISSUE 2016 Rev 1 Installation Manual 3 ThermaQ 2...

Страница 4: ...ponsibilities on both manufacturers and installers The purpose is to ensure that customers are provided with the correct equipment for their needs that it is installed commissioned and serviced in acc...

Страница 5: ...flat base capable of supporting the weight of the cylinder when full The minimum recommended cupboard size is 650mm square Nominal diameter of cylinder is 545mm Areas that are subject to freezing shou...

Страница 6: ...15MPa 1 5 bar working pressure and a 20 litres per minute flow rate Where mains inlet pressures Hot Outlet Non Return Valve Pump Temperature and Pressure Relief Valve Secondary Return Boiler Flow Boi...

Страница 7: ...n order to service the inlet control set Ensure the directional flow arrow on the inlet control set follows the required flow of water See schematic diagram A balanced cold supply is necessary if ther...

Страница 8: ...ld utilise the dual control high limit thermostat as described in Connection to a Boiler section For connection to the lower coil you will require a further two port valve and a single control thermos...

Страница 9: ...0 Specification for the design installation testing and maintenance of services supplying water for domestic use within buildings and their curtilages From the tundish pipework should terminate in a s...

Страница 10: ...of water is drained from the unit Open the hot tap closest to the unit and open the draining tap Note Water drained off may be hot SERVICE AND MAINTENANCE Servicing must be carried out annually and s...

Страница 11: ...ating tap outlet Insecure Pipework Increase the number of pipe clips External works to public mains Wait for works to be completed Reduced water flow Debris from water mains Strip cleanorreplace Inlet...

Страница 12: ...G Is water running from the Tundish Is the water being discharged hot Tundish YES NO Do you have pressure YES NO No fault See the flow chart for T P Valve See the flow chart for Inlet Control Group Ch...

Страница 13: ...erature Pressure Relief Valve YES NO Do you have pressure YES NO No fault with the T P No fault with the T P Replace T P if required Replace T P if required Check temperature setting of the cylinder s...

Страница 14: ...fails replace Dual Stat Test Stat continuity Reset Limit Stat Test Dual Stat continuity Is there power to the Element Thermostat Has the thermostat tripped Does the Immersion Heater work Find correct...

Страница 15: ...3 ThermaQ ENERGY CUT OUT FAULT FINDING Is the Cut Out Thermostat working Test Stat continuity Energy Cut Out Thermostat NO YES Reset Limit Stat No fault with the Thermostat If test fails replace Dual...

Страница 16: ...oming static cold water pressure at the inlet to the system Has a strainer been cleaned of installation debris if fitted Is the installation in a hard water area above 200ppm If yes has a water scale...

Страница 17: ...E 9 Date Engineer Name Company Name Telephone Number Signature SERVICE 8 Date Engineer Name Company Name Telephone Number Signature SERVICE 7 Date Engineer Name Company Name Telephone Number Signature...

Страница 18: ...ns where constant usage and reheating is required titanium immersion heaters must be fitted to comply with the warranty Exclusions 16 The effect of scale build up on the unit or its components 17 Any...

Страница 19: ...SUE 2016 Rev 1 Installation Manual 3 ThermaQ TYPICAL WIRING S PLAN 1 ZONE TYPICAL WIRING Y PLAN COLOUR CODES W WHITE G GREY BL BLUE G Y GREEN YELLOW L LIVE N NEUTRAL C COMMON SL SWITCHED LIVE E EARTH...

Страница 20: ...ISSUE 2016 Rev 1 Installation Manual 3 ThermaQ TYPICAL WIRING S PLAN 2 ZONE COLOUR CODES W WHITE G GREY BL BLUE G Y GREEN YELLOW L LIVE N NEUTRAL C COMMON SL SWITCHED LIVE E EARTH 19...

Страница 21: ...e goods to third parties in the normal course of business In this respect the Buyer shall act in the capacity of the Companies commission agent and the proceeds of such sale 6 6 1 shall be held in tru...

Страница 22: ...ISSUE 2016 Rev 1 Installation Manual 3 ThermaQ NOTES 21...

Отзывы: