24
A Division of:
PP 10
Piping
temperature too
high protection
under cooling
mode
1.
Ambient temperature is too high or the
water temperature is too high in cooling
mode
2.
Refrigeration system is abnormal
1.
Check the scope of using
2.
Check refrigeration system
PP 11
Water
temperature (T2)
too low
protection under
cooling mode
1.
Low water flow
2.
T2 temperature sensor abnormal
1.
Check water pump and waterway
system
2.
Change T2 temperature sensor
Remarks:
1.
In heating mode, if the water out temperature is higher than the set temperature over 7
℃
, LED controller
displays EE04 for water over-heating protection.
2.
In cooling mode, if the water out temperature is lower than the set temperature over 7
℃
, LED controller
displays PP11 for water over-cooling protection.
T
water out
T
SET Temp.
+7
℃
T
SET Temp.
+5
℃
EE04 Water Heating Protection
T
water out
T
SET Temp.
-5
℃
T
SET Temp.
-7
℃
PP11 Water Cooling Protection
7.2 Other Malfunctions and Solutions (No display on LED wire controller)
Malfunctions
Observing
Reasons
Solution
Frequency
Decrease
Compressor
Stop
and
EE04
displays
Normal
Operation
Normal
Operation
Frequency
Decrease
Compressor
Stop
and
PP11
displays
Содержание 09i
Страница 1: ...Swimming Pool Heat Pump User and Service Manual...
Страница 2: ......
Страница 13: ...11 A Division of Dry contact with a relay system Relay to be supplied by Electrician...
Страница 15: ...13 A Division of...
Страница 28: ...26 A Division of 8 Exploded Diagram Model Theratherm 09i...
Страница 31: ...29 A Division of Model Theratherm 14i...
Страница 34: ...32 A Division of Model Theratherm 20i Model Theratherm 25i...
Страница 42: ...40 A Division of 4 4 Parameter Query...
Страница 44: ...42 A Division of 4 7 Water temperature setting...
Страница 46: ......
Страница 47: ...A0141PCI 01...