background image

 

41 

A Division of: 

 

4.5

 

 Parameter Setting 

Parameter Setting

 

 

Parameter 

Range 

Defaults 

Water pump operating mode 

0,1 

Inlet water temperature calibration 

-9.9 - 9.9

 

0.0

 

The parameter value will be updated to the controller display after the adjustment of the slider on APP. On the other 

hand, if the parameter of the controller display is changed, it will also be updated correspondingly on the APP. We 

highly recommend not to adjust these parameters by the App, considering the parameters will be updated easily by 

accident, we will hide this function in next version. Thanks for your attention. 

4.6

 

 Malfunction 

If error occurs, the Malfunction icon turns red. Click it to check the Error. 

 

Содержание 09i

Страница 1: ...Swimming Pool Heat Pump User and Service Manual...

Страница 2: ......

Страница 3: ...ulations in application Incorrect installation against the manual implies the exclusion of the entire guarantee The manufacturer declines any responsibility for the damage caused by an incorrect insta...

Страница 4: ...70 Heating capacity kW 6 6 1 9 9 5 2 2 14 3 9 17 2 4 5 Power consumption kW 1 43 0 27 2 07 0 31 2 78 0 54 3 74 0 63 C O P 7 1 4 6 7 2 4 6 7 2 4 6 7 2 4 6 Compressor type Inverter Compressor Voltage 22...

Страница 5: ...ise level 1m dB A 40 52 40 54 41 56 42 58 Refrigerant R410A Net weight kg 56 73 98 117 Gross weight kg 68 78 113 135 Net dimension mm 1088 380 577 1050 440 709 1050 450 870 Packing dimension mm 1095 4...

Страница 6: ...herm 14i Model Theratherm 20i Theratherm 25i 3 Installation and connection 3 1 Notes Theralux supplies only the Heat Pump itself All other components including a bypass if necessary must be provided b...

Страница 7: ...does not present any problem at all unlike the situation with a gas heater including pilot flame problems ATTENTION Never install the unit in a closed room with a limited air volume in which the air...

Страница 8: ...e the heat exchanger For this reason equipment of this sort must always be fitted in the piping on the downstream side of the heat pump and it is recommended to install a check valve to prevent revers...

Страница 9: ...ow of electrical current to or from the water in the pool Earthing is still required for protection against short circuits inside the unit Always provide a good earth connection Before connecting the...

Страница 10: ...try and avoid excessive contact wear The unit will restart automatically after this time delay expires Even a brief power interruption will trigger this time delay and prevent the unit from restarting...

Страница 11: ...4 2 Accessories Installation Anti vibration bases 1 Take out 4 Anti vibration bases 2 Put them one by one on the bottom of machine like the picture Draining jet 1 Install the draining jet under the bo...

Страница 12: ...union nut clockwise until hand tight Cable wiring 1 To be connected by a licenced Electrician 2 1 2 port is dry contact for heat demand Max 5V Dry contact timer connection Supplied and installed by an...

Страница 13: ...11 A Division of Dry contact with a relay system Relay to be supplied by Electrician...

Страница 14: ...heratherm inverter and the Therachlor system able to use the one pump Making this a one pump system saving power by removing the cost of an extra circulation pump 5 Electrical Wiring 5 1 SWIMMING POOL...

Страница 15: ...13 A Division of...

Страница 16: ...r reference 2 The swimming pool heat pump must be connected earthed although the unit heat exchanger is electrically isolated from the rest of the unit Grounding the unit is still required to protect...

Страница 17: ...al heat pumps It prevents remotely energizing unattended equipment and permits turning off power at the unit while the unit is being serviced 5 2 Installation of the display deportee Photo 1 Photo 2 P...

Страница 18: ...the LED display shows the desired water temperature for 5 seconds then shows the inlet water temperature and the operation mode Press to stop the heat pump unit and show OFF Notice During the paramet...

Страница 19: ...ting Press to set the water temperature directly Parameter checking Press first then press to check the User parameter from d0 to d11 Code Condition Scope Remark d0 IPM mould temperature 0 120 Real te...

Страница 20: ...e P1 Working mode 0 1 1 1 Heating mode 0 cooling mode P2 Timer on off 0 1 0 1 Timer on off is under function 0 Timer on off is out of function The setting of P4 and P5 won t work P3 Water pump 0 1 0 1...

Страница 21: ...on checking adjusting Symbol of automatic start light will flash 6 2 9 6 2 10 Press this button the light will flash the heat pump will operate in Full output only While you choose the Smart the heat...

Страница 22: ...ilure 1 Water flow switch is in bad connection 2 Water flow switch is damaged 3 No Insufficient water flow 1 Check the wiring for water flow switch 2 Change the water flow switch 3 Checkthe water pump...

Страница 23: ...high 2 Driver board is damaged 1 Check if the power is in the normal range 2 Change driver board or main board EE 11 IPM module protection 1 Data mistake 2 Wrong compressor phase connection 3 Compres...

Страница 24: ...change another one EE 19 PFC module high temperature protection 1 PFC module thermal circuit output abnormal 2 Motor is abnormal or damaged 3 Fan blade is broken 4 The screw in the driver board is no...

Страница 25: ...wiring of sensor is loose 1 Re fix the wiring of the sensors 2 Change the sensor PP 02 Outlet water temperature sensor failure 1 The sensor failure or short circuit 2 The wiring of sensor is loose 1 R...

Страница 26: ...if the water out temperature is higher than the set temperature over 7 LED controller displays EE04 for water over heating protection 2 In cooling mode if the water out temperature is lower than the...

Страница 27: ...oller defect 1 Adjust the mode to proper running 2 Replace the defect LED wire controller and then check the status after changing the running mode verifying the water inlet and outlet temperature 3 R...

Страница 28: ...26 A Division of 8 Exploded Diagram Model Theratherm 09i...

Страница 29: ...de 40 Low pressure switch 11 Left panel 41 Low pressure switch 12 Wiring box 42 Transition pipe 13 Front panel 43 Copper pipe 14 Front grill 44 Collective piping assembly 15 Controller 45 Distributor...

Страница 30: ...Exchanger temp sensor clip 55 4 way valve 26 Water in temp sensor TH6 56 Exhaust pipe 27 Electric box 57 Exhaust pipe temp sensor TH3 28 Drainage plug 58 Ambient temp sensor TH1 29 Terminal board 59...

Страница 31: ...29 A Division of Model Theratherm 14i...

Страница 32: ...de 40 Low pressure switch 11 Left panel 41 Low pressure switch 12 Wiring box 42 Transition pipe 13 Front panel 43 Copper pipe 14 Front grill 44 Collective piping assembly 15 Controller 45 Distributor...

Страница 33: ...r temp sensor clip 55 4 way valve 26 Water in temp sensor TH6 56 Exhaust pipe 27 Electric box 57 Exhaust pipe temp sensor TH3 28 Drainage plug 58 Ambient temp sensor TH1 29 Terminal board 59 Ambient t...

Страница 34: ...32 A Division of Model Theratherm 20i Model Theratherm 25i...

Страница 35: ...p sensor TH3 13 Front panel 45 Clip 14 Water proof controller box 46 Sensor casing pipe 15 Front grill 47 Gas return pipe 16 Controller 48 Coil temp sensor TH2 17 Copper pipe 49 Back panel 18 Base tra...

Страница 36: ...itioned for the winter season it is recommended to cover the heat pump with special winter heat pump 6 When the unit is running there is all the time a little water discharge under the unit 10 Warrant...

Страница 37: ...t directly through APP Store or main interface of your mobile phone 2 Controller with WIFI connection 2 1 Turn on the controller under WLAN for 5 second under WLAN until the heat pump BEEPS Then click...

Страница 38: ...on APP 3 1 After install and open the APP Click on the top right to add heat pump If you already operate the step 2 1 and 2 2 controller WIFI connection you could click the next If not you need to fol...

Страница 39: ...37 A Division of 3 3 Click to search heat pump 3 4 Click the online heat pump to enter the main Interface If you long press the heat pump you can rename or delete the heat pump 4 Interface operation...

Страница 40: ...urns to OFF state by touching this button once under the ON state If you operate the ON OFF button on the controller display APP interface will be correspondingly updated to the current status of the...

Страница 41: ...en the timer on off is enable the current time on the controller is synchronized with the network time 4 3 1 Select the Timer ON or Timer OFF 4 3 2 Rotate the pointer to the expected hour and minute 4...

Страница 42: ...40 A Division of 4 4 Parameter Query...

Страница 43: ...justment of the slider on APP On the other hand if the parameter of the controller display is changed it will also be updated correspondingly on the APP We highly recommend not to adjust these paramet...

Страница 44: ...42 A Division of 4 7 Water temperature setting...

Страница 45: ...water temperature by adjusting the slider The setting water temperature on the controller display correspondingly changes after letting go When the setting water temperature on the display changes it...

Страница 46: ......

Страница 47: ...A0141PCI 01...

Отзывы: