background image

4

¾

†

Press MENU

¾

†

Select LIGHT and press OK to confirm

¾

†

Select CHANNEL C1 or C2, confirm with OK

¾

†

Select DELAY TIME, confirm with OK

¾

†

Select ON DELAY, confirm with OK

¾

†

MODIFY HOUR, use the + or – buttons to change hour and 

minute and confirm with OK.

Program switching time in standard program

PROGRAM

MENU

CHANNEL

C1

STANDARD

EXTRA 1

EXTRA 2

EXTRA 3

DELETE ALL

END

u

ª

ª

u

or

Switching 

time for 

one day

NEW

MEM FREE 84

NIGHT  BREAK

LIGHT ON

HOUR

MINUTE

MONDAY

DURATION 

UNTIL

SAVE

COPY

ADD TUESDAY

SAVE

Copy switching to other days of 

the week. The day of the week 

always relates to a start time

Start time

u

u

 

L

A switching time always consists of a start time and an 
end time

 

L

There are 84 memory cells available

Example: Switch on sports hall lighting from Mon–Fri, 7:30 to 

12:00 hrs 

¾

†

Press MENU

¾

†

Select PROGRAM and press OK to confirm

¾

†

Select CHANNEL C1 or C2, confirm with OK

¾

†

Select STANDARD, confirm with OK

¾

†

Select NEW, confirm with OK

¾

†

Select NIGHT BREAK or LIGHT ON, confirm with OK

¾

†

Set required turn-on time (Mo–Fr, 7:30), confirm with OK

¾

†

Set DURATION UNTIL, confirm with OK

¾

†

Select COPY, confirm with OK

¾

†

ADD TUESDAY is displayed, confirm by pressing OK and also 

confirm the days We, Th, Fr by pressing OK.

¾

†

Continue with 

u

 until SAVE is displayed. 

¾

†

Confirm by pressing OK.

Repeat all steps for the turn-off time, however instead of 

selecting ON with 

u

 select OFF and enter 12:00 for hour and 

minute.

Setting special programs

 

The LUNA 121 top3 RC and LUNA 122 top3 RC devices 
feature 3 special programs, which can be used for 
calendar-dependent switching.

 

Each special program can be activated over one or seve-
ral date ranges.

 

There are 3 types of date ranges:

¾

 Fixed date range: 

e.g. start time on 02.04.2018 at 16:00  

end time on 24.04.2018 at 10:00 

¾

 Annually recurring date range: 

e.g. Christmas: 

start time on 24.12 at 18:00 each year  

end time on 26.12 at 23:00 each year

¾

 Easter-dependent date range: 

e.g. Whit Sunday and Whit Monday: 

start time: 49 days after Easter at 00:00  

end time each year: 51 days after Easter at 00:00, 

each year

 

L

The public holiday set can be selected via the app or 
the OBELISK software. The date ranges are created 
automatically.

 

L

24:00 cannot be entered. 0:00 on the following day must 
be programmed.

Set Easter rule

 

L

The EASTER RULE can be set using menu item TIME/DATE

Easter holiday dates in Germany

Days before/after Easter 

Sunday

Public holiday

Start

End

Monday before Lent 

– 48 days  0:00

– 47 days  0:00

Good Friday 

– 2 days  0:00

– 1 day  0:00

Easter Monday 

+ 1 day  0:00

+ 2 days  0:00

Ascension 

+ 39 days  0:00

+ 40 days  0:00

Whit Monday 

+ 50 days  0:00

+ 51 days  0:00

Corpus Christi 

+ 60 days  0:00

+ 61 days  0:00

 

Special program 1  

¾

On and off lux values

¾

Optional 1x night interruption

¾

Optional 1x daytime switch-on

¾

Active in the programmed date ranges  

Example

: The standard program switches on the 

street lighting depending on the lux values.  

A night interruption is programmed from 23:00 to 

04:00. Special program 1 is active in the date range 

from 30 April, 12:00 to 1 May, 12:00. Since no night 

interruption is programmed, the street lighting will 

remain on all night.

 

Special program 2 

¾

Permanent ON

¾

Always on during the programmed date ranges 

Example

: The standard program switches on lighting 

of a neon advertising sign only at night. The special 

program switches on the neon advertising sign per-

manently during a promotion week from 17.04.2018, 

9:00 to 24.04.2018, 18:00.

Содержание LUNA 121 top3 RC

Страница 1: ...ting the time switch Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING click Test connection 45 cable Spring plug in terminal opener Bluetooth OBELISK top3 9070130 DuoFix spring plug in terminal Mount on DIN top hat rails as defined in EN 60715 Switched voltage free Ensure device cannot be switched on Check absence of voltage ...

Страница 2: ...sensor 0 25 1 5 mm2 strip cable by 8 mm max 9 mm max 10mm 8 9 mm ø 5 10 mm 9 mm ca 63mm IP 66 IP 40 Ø 20 mm 4 Device description Display buttons MENU OK OK MENU 0 6 12 18 24 Programmed switching times Date display Channel status C1 C2 ON On OFF Off Time display Days of the week from 1 to 7 Display of the active buttons with the relevant function Activate display Open menu Cancel menu ESC leave men...

Страница 3: ...ration 5 Settings and functions Set lux values LIGHT CHANNEL C1 LUX VALUE LUX ON Switch light off in the mornings Switch light on in the evening LUX OFF MONDAY MONDAY MONDAY 15 lx MONDAY 15 lx SAVE COPY COPY ADD TUESDAY ADD TUESDAY DELAY TIME END MENU u u u u u SAVE L LThe device has been preset at 15 lx for the switch on switch off level Press MENU Select LIGHT and press OK to confirm Select CHAN...

Страница 4: ...e or seve ral date ranges There are 3 types of date ranges Fixed date range e g start time on 02 04 2018 at 16 00 end time on 24 04 2018 at 10 00 Annually recurring date range e g Christmas start time on 24 12 at 18 00 each year end time on 26 12 at 23 00 each year Easter dependent date range e g Whit Sunday and Whit Monday start time 49 days after Easter at 00 00 end time each year 51 days after ...

Страница 5: ...4 light sensors 1 LUNA max 3 light sensors 1 DCF antenna max 10 LUNA Σ max 16 devices LUNA light sensors L LPresetting all connected sensors are active for all chan nels The sensor that sends the lowest lux value is active Activating PIN code The PIN code is set in OPTIONS via the menu L LIf you have forgotten your PIN call the Theben Hotline L LHave the serial number ready OPTIONS NO PIN WITH PIN...

Страница 6: ... not be swit ched at the same time The channels can be interlocked in this case LThe channel lock prevents both channels from switching on at the same time If a channel is already switched on the second channel will not switch on until the first channel is switched off and a waiting time of 1 s has passed If both channels are switched on at the same time channel 1 has priority OPTIONS OPERATING HO...

Страница 7: ... is selected the day of the week or EVERY DAY can be selected and the switchover hour must then be entered only full hours can be entered Finally the system returns to CHANNEL COMBINATION Hour counter The operating hours of the channel relay are displayed and deleted in the OPTIONS menu If the number of operating hours exceeds the value set in the Service menu SERVICE will appear in the display Ex...

Страница 8: ...two way switch Max switching capacity 16 A at 250 V cos ϕ 1 Switching capacity 10 A at 250 V cos ϕ 0 6 Min switching capacity 10 mA 230 V AC 100 mA 24 V AC DC Power reserve 10 years Shortest delay time 1 s Switching accuracy To the second Software Class A Rated impulse voltage 4 kV Pollution degree 2 Glow lamp load 2600 W Halogen lamp load 2600 W Fluorescent lamps KVG uncorrected series corrected ...

Отзывы: