Manual DALI button interface TA 4 S DALI-2
15
Value range "Filter":
For noise reduction, the filter level can be adjusted. The filter number determines from how
many measurement values the average value is calculated.
•
The setting range is 0x00 to 0x0B
The filter delays the measurement. With a filter number of 0x02, the delay is about 0.2
seconds and with 0x0A about 51.2 seconds.
delay [ms] = 2
filter number
* 50 ms.
Value range "beta low/beta high":
If 0x02 has been selected at the sensor type parameter "NTC with known B or Beta", the
associated B or Beta [K] should be set here. B or Beta is a four digit number in [K], which can be
found in the NTC sensor data sheet. In order to be stored in the memory bank, the four-digit
number must first be converted to hex format and then stored in the beta low and beta high
bytes.
Example: B or Beta = 4580 which corresponds to Hex 11E4
•
Beta low = 0xE4 factory setting
•
Beta high = 0x11 factory setting
•
The setting range for beta low
is 0x00 to 0xFF and for beta high 0x00 to 0xFF.
Summary of setting options for parameters
Sensor type
Offset
Range
Hysteresis
Filter
Beta
low/high
0x00
×
×
×
×
0x01
×
×
×
×
0x02
×
×
×
×
×
0x03
×
×
×
Filter number
Measurement value
0x00 factory setting
each measurement value is transmitted
unchanged
0x01
Average value from 2 measurement values (2
1
)
0x02
Average value from 4 measurement values (2
2
)
0x03
Average value from 8 measurement values (2
3
)
…..
…..
0x09
Average value from 512 measurement values
(2
9
)
0x0A
Average value from 1024 measurement values
(2
10
)
0x0B
Average value from 2048 measurement values
(2
11
)