ETS parameters
Manual DALI gateway S64 KNX/S128 KNX
58
Value on DALI Power Fail (System Failure
Level)
0..100%
[100]
Last value
Use this parameter to set the value of a lamp after a loss of DALI power. The value is saved on
the ECG and the device automatically changes to the value when a power loss occurs.
Value on ECG Power Recovery (Power On
Level)
0..100% [
100
]
Last value
Use this parameter to set the value of a lamp after a return of ECG power supply. The value is
saved on the ECG and the device automatically changes to the value when power is restored.
Calculation of Dimming Values
logarythmic
linear
Sets the dimming curve for the ECG is adjusted.
Control ECG Power Line via Object
None
Energy Saving Object 1.. 16
Here you define the object with which the power supply is to be switched off. This parameter
is only visible if this function was previously set on the General
Special Functions parameter
page, see 9.1 General.
Operating hours Calculation
Yes
No
This parameter can be used to set whether an individual operating hour count for the ECG is
desired.
Operating hours Limit value (hours)
(Calculation for operating hours).
1 h..200.000 h
[4000 h]
This parameter is used to set the lamp life at which an individual warning is sent.
Type of the error object
1 bit
1 byte
Here you can define whether the error is to be reported in the form of a bit (Alarm DPT 1.005)
or via a byte object with the information about lamp or ballast errors, see 9.1 General.
Note:
The 1 Byte object is a NON DPT type and will not be implemented in future versions.