1
RAMSES 366/1 top2
3660100
307185
Digital clock thermostat
EN
1. Basic safety information
Danger of death through electric shock or fire!
¾
¾
Installation should only be carried out by a
professional electrician!
WARNING
•
The device is designed for installation on DIN top hat
rails (in accordance with EN 60715)
•
Equivalent to Type 1 B
•
Power reserve (10 years) is reduced if memory card is
inserted (using battery power)
!
OBELISK top2 memory card: Avoid mechanical overload
and contamination during storage/transportation
2. Proper use
•
The digital clock thermostat is intended for time-depen-
dent monitoring and control of the the room temperature
•
Use only in closed and dry rooms of halls, industrial
buildings
•
2 different temperature sensors can be used: a non-
adjustable sensor (9070191) and an adjustable sensor
(9070192), which can be used for temporarily and adjus-
ting the set temperature, if required
Disposal
¾
Dispose of device in environmentally sound manner
3. Installation and connection
Mounting the Digital clock thermostat
Danger of death through electric shock or fire!
¾
¾
Installation should only be carried out by a
professional electrician!
WARNING
click
Leitung 45°
Federsteck-
klemmen-
öffner
Speicherkarte
OBELISK top2
(9070404)
Prüfabgriff
Federsteckklemme
¾
Mount on DIN top hat rails (as defined in EN 60715)
¾
Switched voltage-free
¾
Ensure device cannot be switched on
¾
Check absence of voltage
¾
Earth and bypass
¾
Cover or shield any adjacent live components
Connecting the cable
Wiring diagram
C1
1 2 3
L N
N
L
L
Ext1
max.
100 m
L
max. 50 m
¾
Strip cable to 8 mm (max. 9)
¾
Insert cable in the open DuoFix® plug-in terminal at 45°
L
2 cables per terminal position possible
¾
To open the DuoFix® plug-in terminal, press screwdriver
downwards
Disconnecting the cable
¾
Use the screwdriver to push the load line connection
opener downwards