4
6. Technical specifications
*) Use of T5-FL: When using T5-FL lamps with a comparable wattage, the same number
of electronic ballasts may be connected to the detector’s switching contact as for the T8-
FL. When using the 80W-FL, the number should be halved in comparison to the 58W-FL.
Sensor module ECO-IR 360A
Detection range
horizontal
vertical
360º
120º
Recommended mounting height
2,0m - 3,5m
Maximum range
8 x 8m (Mh. 2,5m)
9 x 9m (Mh 3,0m)
Daylight measurement
Light measurement deactivated
ca. 50 - 1600Lux
„on“
Switch-off delay time for light
2min. - 15min.
Switch-off delay time for presence / HVAC
10min. - 60min.
Sensor module ECO-IR 180A
Detection range
horizontal 180º
Recommended mounting height
ca. 1,6m - 2,2m
Maximum range
< 10m
Daylight measurement
Light measurement deactivated
ca. 50 - 1600Lux
„on“
Switch-off delay time for light
2min. - 15min.
Switch-off delay time for presence / HVAC
10min. - 60min.