6. Test mode
The test mode serves to check the presence detection and the wiring
(Master-Slave parallel circuit operation).
6.1 Setting the test mode with DIP-Switch
● Set DIP switch to «Test» (on all detectors in parallel circuit operation).
1. Start-up phase (30sec)
● Both contacts are closed for 30sec. (LED 20s «on», 10s «off» )
2. Test mode
● In case of movement (LED on), both contacts close.
● In case of absence (LED off), both contacts open after 10sec.
● NOTE: no brightness measurement, detector always in fully automatic mode.
● The detector remains permanently in the test mode.
6.2 Setting the test mode with QuickSet plus
● While setting the test mode with the service remote control QuickSet
plus, the detector jumps the start-up phase and changes directly into the
test mode.
● Test mode ceases automatically after 10 minutes. The detector performs
a reset (see section 4.3).