Thank you for purchasing an Theben HTS presence detector and putting 

your trust in us.

1. Safety

DANGER !

Any work on electrical systems must exclusively be carried out by qualified 

electricians or instructed persons under the direction and supervision of a 

qualified electrician in accordance with the relevant electrotechnical rules! 

Any national safety regulations regarding the manipulation of electrical sys-

tems must be observed! 

The voltage supply must be disconnected prior 

to installation! 

CAUTION !

The device  is maintenance-free. The warranty  terminates  if the device  is 

opened or entered with any kind of object.

Designated use

The presence detector is solely intended for the purpose contractually spe-

cified between the manufacturer and the user. Any other or extended use 

has to be regarded as not complying with the designated use. The manufac-

turer is not liable for any resulting damage.

Содержание 201 0 090

Страница 1: ... compact passage Bedienungsanleitung 2 Notice d utilisation 22 Installation manual 42 Manual de instrucciones 62 Istruzioni per l uso 82 Gebruikershandleiding 102 Bruksanvisning 122 Bruksanvisning 142 Käyttöohje 162 Betjeningsvejledning 182 DK D F GB E I NL S N FIN ...

Страница 2: ...mpact passage Table of contents 1 Safety 43 2 Function and performance characteristics 44 3 Fitting and connection 45 4 Start up 47 5 Additional wiring examples 51 6 Test mode 54 7 Technical specifications 55 8 Warranty declaration 57 9 Troubleshooting 58 ...

Страница 3: ...nal safety regulations regarding the manipulation of electrical sys tems must be observed The voltage supply must be disconnected prior to installation CAUTION The device is maintenance free The warranty terminates if the device is opened or entered with any kind of object Designated use The presence detector is solely intended for the purpose contractually spe cified between the manufacturer and ...

Страница 4: ... by push button or switch Semi or fully automatic operation Push button function room corridor Suitable for fluorescent lamps compact fluorescent lamps halogen incandescent lamps and LEDs Pulse function for staircase lighting timer The switching contact B Presence controls heating ventilation and air conditioning systems The contact closes in case of presence a switch on delay allows a delayed swi...

Страница 5: ...m 105 m2 30 0m x 3 5m 1m 2 5m 72 m2 18 0m x 4 0m 1m 120 m2 30 0m x 4 0m 1m 3 0m 90 m2 20 0m x 4 5m 1m 135 m2 30 0m x 4 5m 1m 3 5m 100 m2 20 0m x 5 0m 1m 150 m2 30 0m x 5 0m 1m Because of the virtually horizontal detection of compact passage to both directions the detection range of tangential t movements of persons is different to the range of radial r movements towards the detector Detection rang...

Страница 6: ...nce for the lighting levels With indirect lighting the artificial light at the detector s mounting location should not exceed 2000 Lux Brightness value 2000 Lux 3 3 Connection A concealed housing should be used for flush mounted fitting of the presence detector compact passage A surface frame is available for sur face mounting N L S A P B2 B1 compact power Master N L Presence e g HVAC ...

Страница 7: ...stance 4 1 Settings for switching contact A Light Potentiometer Brightness threshold LUX Scale Transfer zones no working area approx 2 Bright transfer zones approx 4 Deactivation of brightness measurement on Depending on the installation location natural light intensity furniture reflec tion characteristics of the room and the furniture it may be necessary to correct the settings by 1 2 steps on t...

Страница 8: ...mode auto Fully automatic mode The lighting is switched on automatically man Semi automatic mode The lighting must be switched on manually Push button function room corridor room Manual switching on off possible corridor Detector is used as staircase lighting timer No manual switching off possible Push button Switch control Optional push button or switch operation Multiple push buttons on one cont...

Страница 9: ...d no self learning effect Switch on delay time for presence In case of presence the contact does not close before the set switch on delay has elapsed 0 Contact closes immediately in case of presence Room surveillance function the contact closes only in case of distinct movements effective protection against false alarms 10s ...

Страница 10: ...n after 30sec 2 Service phase 10min The Light contact reacts instantaneously on brightness in order to check the brightness threshold If the brightness is insufficient the lighting is switched on LED on and if the brightness is sufficient the lighting is switched off LED off During the service phase switching of the lighting occurs fully automati cally no semi automatic mode The service phase term...

Страница 11: ...n is done by all detectors together Light measurement occurs on the master only Only set the potentiometer and DIP switches on the master Max 10 detectors can be connected in parallel Use the same phase for all detectors Mark the power modules as master or slave respectively N L S A P B2 B1 compact power Master N L S A P B2 B1 compact power Slave N L Master Slave Lux Master Slave Master Slave DIP ...

Страница 12: ...er Potentiometer and DIP switches are set on each master individually Max 10 detectors can be connected in parallel Use the same phase for all detectors The switching contact Presence can be tapped on any master Mark the power modules as master or slave respectively N L N L S A P B2 B1 compact power Master 1 N L S A P B2 B1 compact power Master 2 Master Lux Master Lux DIP Master Slave Master Slave...

Страница 13: ...lave Master P B2 B1 N L S A P B2 B1 N L S A P B2 B1 N L S A P B2 B1 N L S A P B2 B1 ELPA 1 N L N L out in compact power Master compact power Master 5 4 Detector as staircase lighting timer The master directly controls the lighting The push button starts the master s switch off delay Set DIP switch to corridor to prevent switching off via push button Further slaves can be connected in parallel usin...

Страница 14: ... mode In case of movement LED on both contacts close In case of absence LED off both contacts open after 10sec NOTE no brightness measurement detector always in fully automatic mode The detector remains permanently in the test mode 6 2 Setting the test mode with QuickSet plus While setting the test mode with the service remote control QuickSet plus the detector jumps the start up phase and changes...

Страница 15: ...se 10sec 20min 0 5sec on 10sec off Switch off delay for Presence 10sec 120min Switch on delay for Presence Room surveillance 0sec 10min Power module compact power Mains voltage 230V 10 50Hz Relais output A for Light 230V 10 In line fuse max 10A Max switching capacity Incandescent lamps halogen 1400VA 1200W Max nr of electronic ballasts A relay or contactor must be connected in case of more powerfu...

Страница 16: ...directives 2004 108 EC and of the Low Voltage directive 2006 95 EC Relais output B for Presence potential free Maximum voltage 220V DC 250V AC Maximale switching capacity 50W 50VA Recommended minimum load 0 5mV 10mA Depth Diameter Mounting place 40mm 48mm 70 x 70mm Screw terminals max 2x 2 5mm2 Size of concealed housing Size 1 NIS PMI Ambient temperature 0 50 C Degree of protection IP 40 Article n...

Страница 17: ...you or third parties undertake alterations to the units If the presence detector is connected to a software controlled system the war ranty for this connection is only valid provided the stated interface specification is adhered to We undertake to repair or replace as quickly as possible all supplied components which have become defective or unusable as a result of demonstrably bad material faulty...

Страница 18: ...elapsed self learning effect Disturbing heat sources within the detection range heaters incandescent lamp halogen lamp moving objects e g curtains due to open windows Load el starter devices relay has no interference suppression Lighting keeps switching on and off during the service phase Too much artificial light is falling on the detector Incre ase lux value or reposition the detector Push butto...

Страница 19: ...59 59 GB Subject to change without prior notice Errors and omissions excepted Dimensions compact passage 66 90 46 76 26 5 44 102 5 48 40 40 5 75 63 ...

Страница 20: ... 74 692 369 Fax 49 0 74 74 692 207 hotline theben de Switzerland Theben HTS AG Im Langhag 11 CH 8307 Effretikon Tel 41 0 52 355 17 00 Fax 41 0 52 355 17 01 www theben hts ch Die Kontaktadressen für weitere Länder finden Sie auf www theben de Please find the contact addresses for additional countries on www theben de ...