background image

Page 4

Pump & Pipe 
Installation Instructions

INSTALLATION A:
DIRECT  DISCHARGE  TO  THE  OUTSIDE  OF  THE
BUILDING (Diagram A)

Unplug the main AC pump when installing
the backup pump to avoid electric shock.
Failure to do so could cause serious injury
or death.

1. Cut  a  piece  of  1½”  rigid  PVC  pipe  long

enough  to  reach  from  the  bottom  of  the
sump  pit  to  one  (1)  foot  above  the  floor.
Prime and cement it to the 1½” pipe adapter,
then screw the adapter into the pump.

2. Secure the pump wire so that the plug on the

end will not fall into the sump.  Attach the
wire to the pipe with a piece of tape.

3. Place the pump with the PVC pipe attachment

on the bottom of the sump floor next to the
main AC pump.  The pumps should not touch
each other.  Do not mount the pump to any
existing  pipes;  it  should  be  placed  on  the

floor of the sump.  A brick should be placed
under  the  pump  if  there  are  rocks  or  other
debris  on  the  sump  floor  that  may  clog  the
pump.

4. Attach a union or a check valve to the top of

the 1½” pipe.  This will allow the pump to be
removed easily, should the need arise.

The path of the rest of the pipe and the details
of  each  installation  will  vary.    Using  sound
plumbing practices, route the discharge pipe to
an  exterior  wall  via  the  shortest  path  with  the
fewest  turns.    More  turns  will  reduce  the
pumping capacity.  The pipe section exiting the
building should be on a downward slope so that
the water in the pipe will exit outside instead of
returning to the sump pit.  Be sure to seal the
hole in the wall where the pipe exits, and prime
and cement or clamp all connections securely to
prevent leaking.  (No check valve is needed with
this  method  of  installation  as  long  as  you  use
less than 20 feet of pipe.)

If  you  use  more  than  a  total  of  20  feet of
pipe  in  the  installation  (including  vertical
and horizontal runs), install a check valve in

place of the union.  Make sure it is installed
with  the  arrow  pointing  up,  or  it  will  not
prevent the backflow of water.  When a check
valve is used, a 1/8” hole must be drilled in
the PVC pipe above the Basement Watchdog
pump.  Drill the hole at a 45° angle toward
the  bottom  of  the  sump  to  avoid  splashing
water outside the sump pit.  Make sure the
hole  is  above  the  water  line  and  below  the
check valve.  If a hole is not drilled above the
pump,  an  air  lock  may  prevent  the  pump
from operating.

PUMP
WIRE

PIPE ADAPTER

DRILL 1/8" HOLE

IF CHECK

VALVE USED

FLOOR

JOIST

MAIN 

1/8” HOLE

BRICKS

AC PUMP

RIGID

1-1/2"

PVC PIPE

UNION

OR CHECK

VALVE

CHECK
VALVE

DRAIN   TILE

SLOPE

PIPES

DOWN

BASEMENT

WATCHDOG

PUMP

1

2

3

4

Diagram A

!

DANGER

CAUTION

Содержание Special CONNECT

Страница 1: ...ge for Narrow Sumps 7 Battery Instructions Preparation of the Battery 8 9 Control Unit Connections Positioning the Float Switch 9 Connecting the Pump 9 Installing the Battery Fluid Sensor 10 Connectin...

Страница 2: ...observe the following precautions Someone should be within range of your voice or close enough to come to your aid when you work near a lead acid battery Have plenty of fresh water and soap nearby in...

Страница 3: ...mps or a Y connector and two 2 check valves depending on the installation method you use A surge protector recommended Six 6 quarts of 1 265 specific gravity battery acid 30HDC140S and BW 30F Battery...

Страница 4: ...ove the main AC pump Try to fit the backup pump on the floor of the sump first Make sure there is enough room so that the backup pump and the main pump do not touch each other Select the installation...

Страница 5: ...he discharge pipe to an exterior wall via the shortest path with the fewest turns More turns will reduce the pumping capacity The pipe section exiting the building should be on a downward slope so tha...

Страница 6: ...ed at this time Cut the discharge pipe approximately one 1 foot above the floor Install a check valve on the top of the pipe and tighten the bottom hose clamp Now prime and cement a small piece of 1 P...

Страница 7: ...e path of the rest of the pipe and the details of each installation will vary Using sound plumbing practices route the discharge pipe to an exterior wall via the shortest path with the fewest turns Mo...

Страница 8: ...he Basement Watchdog pump Make sure it is installed with the arrow pointing up or it will not prevent the backflow of water 6 When a check valve is used a 1 8 hole must be drilled in the PVC pipe abov...

Страница 9: ...IS PAGE IF THE TOP OF YOUR BATTERY LOOKS LIKE PHOTO B ON PAGE 9 FOLLOW THE INSTRUCTIONS ON PAGE 9 Contains sulfuric acid Wear eye and clothing protection If battery acid contacts skin or clothing wash...

Страница 10: ...uously The system will NOT warn you if the fluid level is low in this configuration You will need to check your battery every couple of months to see if it needs water If the battery dries out the sys...

Страница 11: ...see if it needs water If the battery dries out the system will not work If you are using a maintenance free battery or sealed AGM battery you will also need to attach the fluid sensor to the POSITIVE...

Страница 12: ...the battery should recharge If no other lights are on this means the terminals may be corroded and the battery cannot charge properly Unplug the charger from the wall outlet Then check the battery ca...

Страница 13: ...he wall outlet You should provide additional protection for the control unit by using a surge protector 10 If any of the alarms are sounding press the YELLOW button on the front of the control panel f...

Страница 14: ...disconnect the battery cables from the battery Then call Glentronics technical support for instructions at 800 991 0466 option 3 You may need to replace the pump 4 Plug the main AC pump back into the...

Страница 15: ...ing up 3 Fan the area around the top of the battery with a piece of cardboard or another non metallic material to remove any hydrogen or oxygen gas that may have been emitted from the battery 4 Remove...

Страница 16: ...be taken to prevent a flood To silence certain alarms for 24 hours press the YELLOW button for 5 seconds until you hear a buzz The alarms will automatically re activate in 24 hours TESTING THE FLOAT S...

Страница 17: ...sit www BasementWatchdog com MAINTENANCE CHECK LIST Maintenance should be performed 1 2 times per year 1 Lift the float switch as described at left 2 Remove all debris from the bottom of the pit and p...

Страница 18: ...ower cord is plugged in securely None if the utility company has instigated brown outs Otherwise reduce the number of other appliances on the circuit Make sure the pump is securely plugged into the ba...

Страница 19: ...ed below GLENTRONICS INC at its option will either repair or replace the product and return it postage prepaid What is NOT Covered by this Warranty This warranty does not cover the cost or value of da...

Страница 20: ...e cage Should one float fail to operate the second float automatically activates the pump The protective cage prevents debris or other wires from interfering with the movement of the float It can be u...

Отзывы: