1. Siren hole
2. Light indicator combined with the touch button "Test"
3. Smoke chamber window, temperature detector behind the net
4. SmartBracket attachment panel
5. On/off button
6. Tamper button
7. QR code
FireProtect Operating Principle
FireProtect operates even without connecting to a security system, determining the smoke
contamination level of the room and temperature increase (
In addition, FireProtect Plus
registers a dangerous CO level
), including a sharp one - in the autonomous mode and
supplied from batteries.
If any fire (smoke) is detected, the detector will switch on a buzzer - the fire siren can be heard
from far, and the logo will light red. When connected to a security system, the detector will also
send an alarm signal to the hub - the user and private security company will receive the
respective notifications.
The detector detects smoke using an optical coupler consisting of an infrared emitter and
photoelectric receiver located in a smoke chamber. If smoke penetrates into the chamber, the
photoelectric receiver detects it based on the distortion of the infrared ray.
As some materials burn without smoke emission, the detector also records temperature
variation. When the function is enabled, the alarm will be actuated, if the room temperature rises
up to 60°С and if the temperature rises by 30° during 30 minutes (even if it is below 60°С).
Additionally, the FireProtectPlus detector model has a function to detect a dangerous CO
level in the room. If a certain concentration of CO in the air is exceeded, the detector
generates an alarm.
The detector activates: