6.2.3.2 STOW PROGRAMMING EXAMPLE
- Press
hold STOW button until light blinks.
- Press
release UP button, monitor will move until hard stop reached. light blinks rapidly.
- Press
release RIGHT button, monitor will move until hard stop reached. light blinks rapidly.
- Press LEFT button to move 45 degrees, Press
release STOW button. light blinks rapidly.
- Press DOWN button to move 90 degrees, Press
release STOW button. light blinks rapidly.
- Press
hold STOW button until light turns off.
and
and
and
and
&
and
6.2.4 OSCILLATE FEATURE
The OSCILLATE feature allows the user to program a repeating pattern to control the horizontal and vertical axes of the monitor. While
in the OSCILLATE pattern, the monitor will pause while the user changes the stream pattern. Pressing any other button will stop the
OSCILLATE pattern.
A label is supplied with each operator station that can be mounted on or near the station as a reminder of how to program the
OSCILLATE pattern. The OSCILLATE pattern needs to be programmed before use. The pattern will be cleared each time power is
cycled to the monitor. For fixed monitors, the monitor may be configured to store the program permanently. See Section 6.2.4.2.
28
6.2.4.1 PROGRAMMING
- Move monitor to starting point of pattern.
- Press and hold OSC button (~5 seconds) until light blinks. Release button. Light will continue to blink while in program mode.
- Move monitor to second point, press OSC button. Light will blink rapidly to acknowledge position.
- Repeat until pattern is complete (up to 65 points).
- Press
hold OSC button until light turns off. Release button.
and
Figure 6.2.4.1
Operator Station Label
OSCILLATE PATTERN PROGRAMMING:
1)
2)
3)
4)
5)
Move monitor to starting point of pattern.
Press & hold OSC button until LED blinks. LED will continue to blink in program mode.
Move monitor to 2nd point, press OSC button. LED will blink rapidly to acknowledge position.
Repeat until pattern is complete.
Press & hold OSC button until LED turns off.
NOTE: PATTERN WILL BE CLEARED UPON POWER LOSS.
TO OSCILLATE:
Pattern must be programmed first.)
Press & release OSC button.
(
TO STOW:
Press & release STOW button.
(Programmable, refer to manual.)
Y5705
800-348-2686
www.tft.com
®
TASK FORCE TIPS
FIRE FIGHTING EQUIPMENT
6.2.4.2 OSCILLATE PATTERN RETAIN FEATURE (DIP #4)
The monitor can be configured so that upon power up, the OSCILLATE
pattern is retained. The OSCILLATE pattern will need be programmed at
least one time (see section 6.2.4.1). To enable the OSCILLATE pattern retain
feature on a monitor follow these steps:
1. Remove lid from monitor operator station.
2. Locate DIP switches on communication board.
3. Slide DIP switch #4 to the ON position.
4. Replace lid. Verify rubber seal is clean and undamaged. Verify that
no wires are caught between lid and box.
5. Program OSCILLATE pattern.
Figure 6.2.4.2
Oscillate Pattern Retain Setup
ON
CTS
12
3
4