FL-B101D40PF Power factor (D0109) Manual
Page 9
Clear Lockable NEMA 4X
Splash Proof Lens Cover
P/N.(OP-N4/144X36 )
133.5mm
(5.27")
Mosaic
Fitting
9/64 DIN
cutout
spacer
To open rear cover,
use a small flat
blade screw driver.
Press down lightly
to release catch and
leaver outwards.
SIDE VIEW
137.7mm
(5.42")
9/64 DIN
cutout
spacer
142.3mm
(5.62")
Max. panel thickness
43mm
(1.7")
For additional strength,
extra Mounting Slide Clips
can be ordered and doubled up
one behind the other.
P/N. (75-DMC144X36)
4.5mm
(0.18")
Metal Surround Case
P/N.(OP-MTL144X36) is pre-installed
at the factory and cannot be removed
without damage to the case.
Two bezel Trim
Strips are supplied with
each Panel Adaptor
Panel Adaptor to fit existing 6" Edgewise
Pointer Meter Cut-Outs P/N.(OP-PA/144x36)
Adaptor uses wide jaw mounting slide
clips.P/N.(75DMC14436B)
When extra panel
mounting tightness is
required,
order the optional
screw mount
clip.
P/N
.(O
PM
TL
CL
IP)
FRONT VIEW
144mm
(5.69")
36mm
(1.42")
4mm
(0.16")
typical
9/64 DIN
36x144 mm
100
0
10
30
50
70
90
20
40
60
80
4
3
2
1
P
SP
PANEL CUTOUT
138mm
(5.45")
33mm
(1.3")
Snug
Fitting
Loose
Fitting
8 places
7.5mm(0.3")
3.5mm(0.14")
4 places
4 places
32.2 mm
(1.27")
Mosaic
Fitting
133mm
(5.25")
135.2mm
(5.34")
3mm(0.12")
9/64 DIN
cutout
spacer
Case will mount in standard DIN cutouts
Various
bezel colors
are available.
Black is
standard.
The Metal Surround
case uses Metal
Screw Mount Clips
and has a max.
panel thickness
mounting of
7mm(0.28")
TOP VIEW
5mm
(0.20")
117.5mm
(4.64")
18.3mm (0.72")
Straight-thru
Connector
31mm
(1.22")
34mm
(1.34")
Mosaic Fitting
Right-angled
Connector
6mm
(0.24")
10mm
(0.39")
26.5mm (1.05")
Push-On Connector
for FI series IO board
The adapter snaps on
the 36x144 mm
(1.42"x5.69") case and
enables single unit or
stack mounting in an
existing 6" edgewise
pointer meter cut-out.
100
0
25
50
75
100
0
25
50
75
SP1 SP2
SP3 SP4
Zero Span
Zero Span
Panel adaptor plates are
available to retrofit most
existing panel cutouts.
31mm
(1.22")
These dimensions are
increased by 2mm (0.08") when
the
metal surround case is installed.
For extra strength in portable applications,
the 8 DIN spacers should be snipped
off and the
Mosaic fitting cutout used.
Case Dimensions
Installation Guidelines
Installation
1� Install and wire meter per local applicable codes/reg-
ulations, the particular application, and good installation
practices�
2� Install meter in a location that does not exceed the
maximum operating temperature and that provides
good air circulation�
3� Separate input/output leads from power lines to
protect the meter from external noise� Input/output
leads should be routed as far away as possible from
contactors, control relays, transformers and other noisy
components� Shielding cables for input/output leads is
recommended with shield connection to earth ground
near the meter preferred�
4� A circuit breaker or disconnect switch is required to
disconnect power to the meter� The breaker/switch
should be in close proximity to the meter and marked as
the disconnecting device for the meter or meter circuit�
The circuit breaker or wall switch must be rated for the
applied voltage (e�g�, 120VAC or 240VAC) and current
appropriate for the electrical application (e�g�, 15A or
20A)�
5� See
Case Dimensions section
for panel cutout infor-
mation�
6� See
Connector Pinouts section
for wiring�
7� Use 28-12 AWG wiring, minimum 90˚C (HH) tempera-
ture rating� Strip wire approximately 0�3 in� (7-8 mm)�
8� Recommended torque on all terminal plug screws is
4�5 lb-in (0�51 N-m)�