Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com
Page 10
FL-B101Q-HZ_manual (d0059)
!
WARNINg
AC and DC power supply voltages are hazard-
ous. Make sure the power supply is isolated
before connecting to the meter.
COM
1&3
NO3
SP3
NO
SP1/3
COM
SP1
NC
SP2
N1
SP1
NO
SP2/4
COM
SP2
NC
SP2
NO
LOCK
COMMON
DIM
NC1
SP3
COM
2&4
NC2
NO4
SP4
NO1
SP1
NO2
SP2
8 9 10 11 12 13 14 15
17 18 19 20 21
23 24
1-6
See Leopard Family Input
Signal Conditioning Moduls
Analog
Analog
Output –
AC
Neutral
AC
Line
– DC
+ DC
or
This meter uses plug-in type screw terminal connectors
for all input and output connections. The power supply
connections (pins 23 and 24) have a unique plug and
socket outline to prevent cross connection. The main
board uses standard right-angled connectors.
Replacement 2-, 3-, and 4-pin plug connectors are avail-
able.
Input Signal – Pins 1 to 6
Pins 1 to 6 are reserved for the input signal conditioner.
See the data sheet for the selected input signal conditioner.
Pins 8 to 15 – Relay Output Pins
Pin 8 SP3 NO. Normally Open 4 Amp Form A.
Pin 9 SP1/3 COM. Common for SP1 and SP3.
Pin 10 SP1 NC. Normally Closed 9 Amp Form C.
Pin 11 SP1 NO. Normally Open 9 Amp Form C.
Pin 12 SP4 NO. Normally Open 4 Amp Form A.
Pin 13 SP2/4 COM. Common for SP3 and SP4.
Pin 14 SP2 NC. Normally Closed 9 Amp Form C.
Pin 15 SP2 NO. Normally Open 9 Amp Form C.
Pins 17 to 21 – Rear Panel Switches
Pin 17 ANALOg OuTPuT (+). mA (0 to 20 mA/4 to 20 mA)
or V (0 to 10 V) output is header selectable.
Pin 18 ANALOg OuTPuT (–). mA (0 to 20 mA/4 to
20 mA) or V (0 to 10 V) output is header selectable.
Pin 19 Programming LOCk. By connecting the LOCK pin
to the COMMON pin, the meter's programmed
parameters can be viewed but not changed.
Pin 20 COMMON. To activate the LOCK or DIM functions
from the rear of the meter, the respective pins have
to be connected to the COMMON pin. This pin is
connected to the internal power supply ground.
Pin 21 DIM. By connecting the display dim (DIM) pin to
the COMMON pin, the display brightness setting
is halved.
Pins 23 and 24 – AC/DC Power Input
Auto-sensing AC/DC power supply. For voltages between
85-265 V AC / 95-300 V DC (PS1) or 15-48 V AC / 10-72 V
DC (PS2).
Pin 23 AC Neutral / –DC. Neutral power supply line.
Pin 24 AC line / +DC. Live power supply line.
Controls and Indicators
Connector Pinouts
Controls and Indicators
Pin Descriptions
Note: The sequence of setpoint outputs is 3-1-4-2, enabling delay on
make (dom) and delay on break (dob) to be used with both Form “C”
relays.
Connectors
Standard plug-in screw terminal blocks provided by the Manufacturer
WARNINg
AC and DC input signals and power
supply voltages can be hazardous.
Do Not connect live wires to termi-
nal blocks, and do not insert, remove or han-
dle terminal blocks with live wires connected.
!
Straight-thru
Screw Terminal Plug
Part Numbers:
93-PLUG2P-DS....2 pins
93-PLUG3P-DS....3 pins
93-PLUG4P-DS....4 pins
Pin Socket
Pin Socket
Pin Socket
Pin Socket
Right-angled
Screw Terminal Plug
Part Numbers:
93-PLUG2P-DR.....2 pins
93-PLUG3P-DR.....3 pins
93-PLUG4P-DR.....4 pins
Input Power
Screw Terminal Plug
Part Number:
93-PLUG2P-DP
Straight-thru Input Power
Screw Terminal Plug
Part Number:
93-PLUG2P-SP
93-PLUG5P-DR....5 pins
93-PLUG6P-DR....6 pins