Page 5
CL-B101D40RPM(d0097) manual
Example
Example
From Pulses Per
Revolution, Range
Selection Mode
See Page 4
STEP A
STEP B
See Example Above
of Bargraph Display
Scale Range
To Digital Span Selection
for Analog Range Output or
Bargraph Center Point
Display Mode Selection
on Page 6
DIGITAL SPAN SELECTION
FOR BARGRAPH DISPLAY
STEP A Enter the Calibration Sub Menu Mode
1) Press the
P
and buttons at the same time. Display toggles
between [CAL] and [oFF].
2) Press the
P
button. Display toggles between [bhi] and the
p re v i o u s setting.
STEP B Set the Digital Span of the Bargraph Display (See example
above)
1) Using the and buttons, adjust the display to the
desired
high parameter reading, e.g. 6000 counts.
2) Press the
P
button. Display toggles between [bLo] and the
previous setting.
3) Using the and buttons, adjust the display to the
desired
low parameter reading, e.g. 4000 counts.
4) Press the
P
button. Display changes from [4000] to [dP].
Note:
If at this point, the display skips directly to STEP E and toggles
between [Cto] and [oFF], the software is detecting that the optional analog
output hardware is NOT installed.
Digital Span Selection For Bargraph Display
Bargraph does not light
up for Input Signals up to
3999 counts
Bargraph lights up for
Input Signals above
4000 counts
Bar
High
Bar
Low
Bar
High
Bar
Low
0
25
75
100
50
0
25
75
100
50
No bargraph display
Digital display
No bargraph display
Digital display
An example of setting the
digital span of the bargraph
display to be different than
the digital display range
The bargraph can be set to display full scale (0-101 bars) any portion
of the digital reading from a minimum of 100 counts to a maximum of
12,000 counts. This provides higher resolution bargraph indication for
those applications where the normal operating input signal range is less
than the desired full scale display range of the digital display.
For Example:
If the full scale range of the meter has been set from -1999 to
9999 (0-12,000 counts), but the normal operating range of the
input signal is between 4000 & 6000. The bargraph high parame-
ter [bhi] can be set to 6000 and the bargraph low parameter [bLo]
can be set to 4000.
This means that although the meter could digitally display a signal
from -1999 to 9999 (0-12,000 counts), the bargraph display only
begins to function at a reading of 4000, and reaches full scale
indication at a reading of 6000. Although the digital display will
continue reading up to 9999 before indicating overrange, the bar-
graph display will indicate its overrange by flashing for readings
above 6000.