background image

Page 3

CL-B101D40RPM(d0097) manual

The CL-B101D40RPM is an intelligent bargraph meter with a hier-

archical software structure designed for easy programming and 

operation, as shown below in the software logic tree.

Software Logic Tree

Peak

[PEAK]

Reset

PEAK

Reset

VALY

Valley

[VALY]

[orAn]

[rEd]

NOTE: Will only 

appear if a tricolor 

display is installed

[orAn]

[rEd]

[orAn]

[rEd]

[orAn]

[rEd]

[orAn]

[rEd]

BARGRAPH COLOR 

PROGRAMMING MODE

See Page 9

Tricolor Bargraph

The tri-color bargraph is 

designed like a traffic light, to 

display either red, orange or 

green, but only one color at a 

time. The color to be displayed 

is selected in two ways.

The first step is to select the 

color to be displayed when the 

bar is “below” whichever set 

point is set to the lowest 

position.

The second step is to select the 

color to be displayed when the 

bar is above each specific 

setpoint, regardless of the order 

or position to which the set 

points are set.

However, if two or more 

setpoints with differently 

specified colors are positioned 

at the same set point value, the 

color specified for the set point 

with the highest identifying 

number will be displayed. When 

setpoints are set to the same 

value, the SP4 color overrides 

the SP3 color, the SP3 color 

overrides the SP2 color, and the 

SP2 color overrides the SP1 

color.

Set Setpoint 1

[SP1]

Delay-on-Make

[doM]

Delay-on-Break

[dob]

Relays 

Activation 

[rLYS] 
(h) High
 the 

relay 

energizes 

when the 

setpoint is 

exceeded.
(L) Low 

the relay

energizes 

below the 

setpoint. 

Setpoint 2

[SP2]

Setpoint 2

[SP2]

Setpoint 1

[SP1]

Setpoint 3

[SP3]

NOTE: [dom] [dob] 

Functions are only 

available for SP1

abd SP3 

0 to 9999

seconds

0 to 9999

seconds

Hysteresis

[hYSt]

Hysteresis

[hYSt]

Bar Color

[coL]

Hysteresis

[hYSt]

Hysteresis

[hYSt]

Setpoint 3

[SP3]

Setpoint 4

[SP4]

Setpoint 4

[SP4]

Operational Display

MAIN  MENU

PEAK & VALLEY 

VIEW & RESET

BRIGHTNESS AND

SETPOINT VIEW MODE

Bargraph Center Point

Display Selection [cto]

This branch will

only appear if

the analog

output option

is installed

Back to

Operational

Display

Digital Display

ON/OFF 

Selection [diSP]

Sub-menu MODE

Calibration Mode

Calibration

Input

Calibration

Output

Calibrate Analog 

Output Low

[cLo] 

Calibrate Analog

Output High

[chi]

Select the Digital

Reading at which

the Analog Output

Hi [chi] will occur

Select the Digital

Reading at which

the Analog Output

Lo [cLo] will occur

This branch will only appear 

if the analog output option 

is installed 

DIGITAL SPAN SELECTION

FOR ANALOG RANGE OUTPUT

See Page 6

DIGITAL DISPLAY ON/OFF

See Page 6

BARGRAPH CENTER POINT

DISPLAY MODE SELECTION

See Page 6

TWO POINT ANALOG OUTPUT

RANGE SETTING AND CALIBRATION

See Page 7

Bargraph Display

Scale Lo Range

Setting [bLo]

Bargraph Display

Scale hi Range

Setting [bhi]

DIGITAL SPAN SELECTION

FOR BARGRAPH DISPLAY

See Page 5

Goes directly

to Zero setting

if Analog Output

is not installed

PULSES PER 

REVOLUTION, RANGE

SELECTION

+

4.00

+

20.00

1  Dimmest

2  Dim        

3  Bright     

4  Brightest

SETPOINT SETTING  AND 

RELAY CONFIGURATION MODE

See Page 8

L or h

L or h

L or h

L or h

Display

Brightness

            [br]

Delay-on-Make

[doM]

Delay-on-Break

[dob]

0 to 9999

seconds

0 to 9999

seconds

Sub-menu MODE

Software Version is Displayed on Power-up

When power is applied, all segments of the bargraph and dig-

ital display light up for 3 seconds.  The version number of the 

installed software is then displayed for 2 seconds, after which, 

the operational display indicates the input signal.

15 Second Program Timeout

Except for ZERO and SPAN settings in the Two Point Digital Calibration Mode 

and the Analog Output Range Setting and Calibration Mode (cLo and chi), the 

meter has a 15 second program timeout. If no buttons are pressed for 15 

seconds in any of the other programming sequences, the meter will exit the 

programming mode and return to the operational display. Any program chang-

es that were made prior to pressing the 

P

 button in the preceding step will 

not be saved.

Содержание CL-B101D40RPM

Страница 1: ...Conventions 2 Input Specs Depends on Input signal conditioner A D Converter 14 bit single slope Accuracy 0 05 of reading 2 counts Temp Coeff 100 ppm C Typical Warm up time 2 minutes Conversion Rate 10 conversions per second Typical Digital Display 4 digit 0 56 LED red std green optn Range 0 to 9999 counts Bargraph Display 101 segment 235º circular bar red std green optn or tricolor optn Polarity A...

Страница 2: ...xplain software programming procedures logic diagrams are used to visually assist in following the programming steps The following symbols are used throughout the logic diagrams to represent the buttons and indicators on the meter Programming Conventions X XXX XX XX XXX X XXXX XXXX Front Panel Buttons Program Button The P button is used to move from one program step to the next When pressed at the...

Страница 3: ...INT VIEW MODE Bargraph Center Point Display Selection cto This branch will only appear if the analog output option is installed Back to Operational Display Digital Display ON OFF Selection diSP Sub menu MODE Calibration Mode Calibration Input Calibration Output Calibrate Analog Output Low cLo Calibrate Analog Output High chi Select the Digital Reading at which the Analog Output Hi chi will occur S...

Страница 4: ...lution PPR 1 Using the and buttons enter the number of pulese per revolution Any number between 1 and 9999 may be enterd 2 Press the P button Display toggles between rg and the previous range setting STEP D Select the Range 1 Using the and buttons selete the required range There are three ranges with resolutions of 0 1 max 999 9 RPM 1 max 9999 RPM and 10 RPM max 99 99 x 10000 RPM 2 Press the P but...

Страница 5: ...p for Input Signals up to 3999 counts Bargraph lights up for Input Signals above 4000 counts Bar High Bar Low Bar High Bar Low 0 25 75 100 50 0 25 75 100 50 No bargraph display Digital display No bargraph display Digital display An example of setting the digital span of the bargraph display to be different than the digital display range The bargraph can be set to display full scale 0 101 bars any ...

Страница 6: ... is off If the digital display is selected to be off pressing any button to make programming changes or to view setpoints activates the digital display When the procedure is complete the digital display will then automatically switch off The Display Bargraph settings are now complete Operational Display STEP E STEP F See Example of Bargraph Center Point Display Mode Selection Above From Digital Sp...

Страница 7: ...any value from 0 3 mA to 18 mA mA output selected or from 0 6 V to 8 V volt output selected However the output of cLo must always be less than the value selected for chi If a reversed analog output is desired the values selected to establish the Digital Span can be reversed see top of page 6 For digital readings outside the Digital Span selected the analog output will not go any lower than the cal...

Страница 8: ...to the desired hysteresis hYSt value 2 Press the P button Display toggles between SP2 and the previous SP2 setting STEP F Set Setpoint 2 SP2 1 Using the and buttons adjust the display to the desired SP2 value 2 Press the P button Display toggles between hySt and the previous hySt setting STEP G Set the Hysteresis hYSt Setting for Setpoint 2 1 Using the and buttons adjust the display to the desired...

Страница 9: ...Bargraph Color when the bar is ABOVE SP2 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP3 and the previous color setting STEP T Select Bargraph Color when the bar is ABOVE SP3 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP4 and the...

Страница 10: ...rminal plugs and do not insert remove or handle screw terminal plugs with live wires connected 17 16 14 15 8 9 10 11 See Leopard Family Input Signal Conditioning Modules 1 2 3 4 5 6 21 20 19 Relay Outputs Reserved for RS 485 LOCK COMMON No Function DIM ANALOG OUTPUT AC Neutral DC AC Line DC ANALOG OUTPUT 29 28 27 26 25 24 23 22 Standard plug in screw terminal connectors provided by Texmate Connect...

Страница 11: ...SP4 SP2 Relay Modules with 2 Non Isolated 4A Form A Relays and 2 Non Isolated 9A Form C Relays 29 28 27 25 26 24 23 22 DL Series Options Order Code OR51 OR52 OR53 OR54 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 Relay Modules with 4 Independent 300V 210mA DC only 29 28 27 25 26 24 23 22 DL Series Options Order Code OR31 OR32 OR33 OR34 5A 5A 5A 5A 5A ...

Страница 12: ...s for input output leads is recommended with shield connection to earth ground near the meter preferred 4 A circuit breaker or disconnect switch is required to disconnect power to the meter The breaker switch should be in close proximity to the meter and marked as the disconnecting device for the meter or meter circuit The circuit breaker or wall switch must be rated for the applied voltage e g 12...

Страница 13: ...en LED Bargraph w 4 Digit Red DPM Horizontal 20 HRG Red LED Bargraph w 4 Digit Green DPM Horizontal 15 HTG Tri Color Bargraph w 4 Digit Green DPM Horizontal 60 HTR Tri Color Bargraph w 4 Digit Red DPM Horizontal 50 DSGG Dual Scale Green LED Vertical Bargraph w 4 Digit Green DPM 30 DSGR Dual Scale Green LED Vertical Bargraph w 4 Digit Red DPM 20 DSRG Dual Scale Red LED Vertical Bargraph w 4 Digit G...

Отзывы: