Page 8
CL-B101D40PS Manual (d0096)
101.60
4.000
42.85
1.687
42.85
1.687
42.85
1.687
42.85
1.687
6.50
0.256
113.79
4.480
113.79
4.480
56.90
2.240
56.90
2.240
17.50
0.689
97.77
3.849
119.70
4.713
13.70
0.539
1/4"-28UNF
Panel Cutout
5.0
0.197
R4
0.157
16.30
0.642
13.70
0.539
4.80
0.189
screw-10-32 UNF
8
0.315
7
0.276
16.30
0.642
13.70
0.539
2.60
0.102
6.32
0.249
screw-1/4”-28 UNF
Case Dimensions
Operational Display
Sub-menu
MODE
STEP A Calibration
Mode
STEP B Calibration
Mode
STEP E
Calibrate
Analog
Output
Lo
STEP F
Calibrate
Analog
Output
Hi
Will only appear if the analog
output option is installed
To Digital Span Selection
for Bargraph Display
See Page 5
To Two Point Digital
Calibration Mode
See Page 4
Operational Display
TWO POINT ANALOG OUTPUT
RANGE SETTING AND CALIBRATION
+
x
–
x
4.00
+
x
–
x
20.00
Determine if the Analog Output Selection Header is in the 4 to 20mA (0-20mA) position or the 0
to 10VDC position. If necessary, the module may have to be removed and the header position
changed (see Component Layout below).
Note: Always disconnect power from the meter before removing the analog output module to
adjust the mA or Volts output selection header and reinstalling it. When power is reconnected, the
meter’s software will automatically detect the presence or absence of the analog output module.
STEP A Enter the Calibration Mode
1) Press the
P
and buttons at the same time. Display toggles between [cAL] and [oFF].
2) Press the or button. Display changes from [oFF] to [on].
3) Press the
P
button. Display toggles between [cAL] and [out] input calibration.
Note
: If at this point the display skips directly to toggle between Zero and the previous Zero
setting, the software is detecting that the optional analog output hardware is NOT installed.
STEP B
Enter the Two Point Analog [ouT] Output Range Setting and Calibration Mode
1) Press the
P
button. Display toggles between [cLo] and an internal scale factor.
STEP E
Set or Calibrate [cLo] the Low Analog Value of the Analog Output Range
1) Connect a multimeter to analog output pins 17 and 18 (see Rear Panel Pinouts
on page 10). Using the and buttons, adjust the analog output to the desired
low value as measured on the multimeter. cLo may be adjusted to any value from
–0.3 mA to 18 mA (mA output selected) or from –0.6 V to 8 V (volt output selected).
However, the output of cLo must always be less than the value selected for chi. If
a reversed analog output is desired, the values selected to establish the Digital
Span can be reversed (see top of page 6). For digital readings outside the Digital
Span selected, the analog output will not go any lower than the calibrated value set
for cLo. However, the analog output will linearly rise above the value set for chi, up
to the the maximum analog output capability (see chi below).
2) Press the
P
button. Display toggles between [chi] and an internal scale factor.
STEP F
Set or Calibrate [chi] the High Analog Value of the Analog Output Range
1) Using the and buttons, adjust the analog output to the desired high value
as measured on the multimeter display. chi may be adjusted to any value from 18
mA to 24 mA (mA output) or from 8 V to 10.3 V (volt output). However, the value
must be higher than the value selected for cLo. For digital readings outside the
Digital Span selected, the analog output will linearly rise above the value set for chi,
up to the maximum analog output capability.
2) Press the
P
button. The meter exits the calibration mode and returns to the
operational display.
Note:
The analog output range established by the values selected for cLo and chi will occur, auto-
matically scaled, between the two digital values selected for AnHi and AnLo. However, the analog
output can linearly rise above the chi value set for digital readings outside the digital span
selected. See Digital Span Selection on page 6.
Two Point Analog Output Range Setting and Calibration
Two Point Analog Output Range Setting and Calibration